Connecting the RER601/603 to an Ethernet network
There are two different ways to configure the network settings: via serial port or Web Browser
interface. It is recommended to use the Web Browser to configure the network connection
settings.
Method 1: Setting IP Address Using Web Browser (Recommended)
1. Connect the cross-over Ethernet cable between the RER601/603 and your computer.
2. Configure your computer to use the same IP address space than the RER601/603 (laptop IP
for example 10.10.10.11 with netmask 255.0.0.0). Check the connection to the RER601/603
with ping utility.
3. Connect to the RER601/603 using your web browser. The default IP address of the
RER601/603 is 10.10.10.10 (netmask 255.0.0.0).
4. From the initial page click Start configurator and enter login information in the following
page. Username is root and by default no password is set (just leave the field empty).
5. Navigate to Network page
6. Enter the IP address and other network settings of your choice and click Apply
then Commit
7. Reboot the RER601/603 for the settings to take effect.
1
2
3
4
NOTE: You can check the current network status from the Network-->Summary subpage.
ABB
Wireless Gateway RER601/603
Quick Start Guide
and from there to Ethernet subpage.
1
4
to store the settings.
Figure 1. RER601/603 Configurator screen, Ethernet settings