SPECIFICATIONS

UNIT
Total cooling capacity
Nominal absorber power
Air flow (max./min.)
Available static power. (1)
Chilled water flow rate
Chilled water pressure drop
Net weight
Sound level
(2)
(LP)
H
Large
Dimensions
W
Hydraulic connections
(*) Inlet air temperature: 27ºC DB / 19ºC WB
Inlet/Outlet water temperature: 30ºC / 35ºC
(1) With minimum air flow admissible
(2) Sound level has been tested at a distance of 2m from the unit.
ELECTRICAL SPECIFICATIONS
VOLTAGE
NOMINAL ABSORBER POWER
Compressor
Indoor fan
TOTAL
RUNNING CURRENT
Nominal running current
Maximum running current
Starting current
SNE 2,8K
W (*)
8.300
Kw
2,68
3
1800/950
m /h
Pa
120
l/h
1885
KPa
24
Kg
100
dB(A)
50
(mm)
1125
(mm)
635
(mm)
515
3/4" G
SNE 2,8K
2,50
Kw.
Kw.
0,18
Kw.
2,68
14,0
A
18,0
A
91
A
3
SNE 3K
10.700
3,18
2050/1100
100
2390
30
110
52
1125
635
515
3/4" G
SNE 3K
230V /1Ph
230V / 400V 3Ph
2,78
0,40
3,18
17,4
9,5/5,5
23,0
16,0/10,0
90
78 / 39
SNE 4K
13.600
3,82
2050/1450
80
3000
16
120
53
1125
635
515
1" G
SNE 4K
3,42
0,40
3,82
11,5/6,8
20,0/12,0
106 / 53