Wiring Examples - Panasonic KT9 Instruction Manual

Hide thumbs Also See for KT9:
Table of Contents

Advertisement

Notice
• The terminal block of KT9 series is designed to be wired from the left side.
The lead wire must be inserted from the left side of the terminal, and fastened
with the terminal screw.
• Dotted lines show options.
• If A2 (option) and Heater burnout alarm (option) are applied together, use
terminals 12-13 for A2, and 9-10 for the Heater burnout alarm.
• If the Heating/Cooling control (option) and Heater burnout alarm (option) are
applied together, use terminals 9-10 for the Heating/Cooling control, and 12-13
for the Heater burnout alarm.
• When only Heater burnout alarm option is applied, use terminals 9 and 10.
Lead wire solderless terminal
Use a solderless terminal with an insulation sleeve in which an M3 screw fits as shown
below.
Solderless
terminal
Nichifu Terminal Industries CO.,LTD.
Y type
Japan Solderless Terminal MFG CO.,LTD.
Nichifu Terminal Industries CO.,LTD.
Round type
Japan Solderless Terminal MFG CO.,LTD.

4.2 Wiring examples

Notice
• To extend a thermocouple's lead wire, be sure to use a compensating lead wire in
accordance with the sensor input specification. (If any other compensating lead wire
is used, a temperature indication error may be caused.)
• Use the 3-wire RTD according to the sensor input specifications of this controller.
• This controller does not have built-in power switch, circuit breaker or fuse.
It is necessary to install them in the circuit externally, near the controller.
(Recommended fuse: Time-lag fuse, rated voltage 250V AC, rated current 2A)
• For a 24V AC/DC power source, do not confuse polarity when using direct current (DC).
• When using a relay contact output type, use a relay externally according to the
capacity of the load to protect the built-in relay contact.
• When wiring, keep the input wire (Thermocouple, RTD, etc.) away from AC sources
or load wires to avoid external interference.
• Use a thick wire (1.25 to 2.0mm
Manufacturer
3.2mm
(Fig. 4.1-2)
2
) for grounding.
Model
TMEV1.25Y-3
VD1.25-B3A
TMEV1.25-3
V1.25-3
13
Tightening torque
0.63N•m
3.2mm