OUT2 high limit setting
• Sets the high limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: OUT2 low limit value to 105%
(Setting higher than 100% is effective to DC current output type.)
OUT2 low limit setting
• Sets the low limit value of OUT2.
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –5% to OUT2 high limit value
(Setting less than 0% is effective to DC current output type.)
Overlap band/Dead band setting
• Sets overlap band and dead band value for OUT1 and OUT2.
+ Set value: Dead band
– Set value: Overlap band
• Not available if OUT2 is ON/OFF action or if Heating/Cooling control
(option) is not applied
• Setting range: –100.0 to 100.0
DC input: –1000 to 1000 (The placement of the decimal
OUT2 ON/OFF action hysteresis setting
• Sets ON/OFF action hysteresis for OUT2.
• Available when OUT2 is ON/OFF action or when Heating/Cooling
control (option) is applied
• Setting range: 0.1 to 100.0
For DC input, 1 to 1000 (The placement of the decimal
A1 type selection
• Selects A1 type.
• Selecting item
No alarm action
High limit alarm
Low limit alarm
High/Low limits alarm
High/Low limit range alarm
Process high alarm
Process low alarm
High limit alarm with standby
Low limit alarm with standby
High/Low limits alarm with standby:
( )
point follows the selection)
( )
point follows the selection)
:
:
:
:
:
:
:
:
:
24
100%
0%
0.0
1.0
No alarm action