Name And Functions Of The Sections; Mounting To The Control Panel - Panasonic KT4 series Instruction Manual

Hide thumbs Also See for KT4 series:
Table of Contents

Advertisement

(5) Heating/Cooling control (OUT2)-- 0: Not available, 4: Non-contact relay output
(6) Heater burnout alarm -------------- 0: Not available, 1: Available (5A), 2: Available (10A), 3: Available
(7) Serial communication ------------- 1: Available (The number is indicated only when the serial
1.2 How to read the rated label
The rated label is attached to the case.
When Heater burnout alarm is added, CT rated current is written in the bracket.
(1)
A K T 4 1 1 1 1 0 0 1
(2)
No.
(1) Model number, supply voltage, input type, output type, etc. are entered.
(2) Lot number is entered.

2. Name and functions of the sections

(1)
(2)
(3)
(10) (11) (12) (13)
(Fig. 2-1)
(10) Increase key : Increases the numeric value.
(11) Decrease key : Decreases the numeric value.
(12) Mode key
(13) OUT/OFF key : The control output is turned on or off. If this key is pressed for approx. 1 second,
Notice
When setting the specifications and functions of this controller, connect terminals 1 and 2 for power
source first, then set them referring to "5. Setup" and "7. Operation flowchart" before performing
"3. Mounting to the control panel" and "4. Wiring".

3. Mounting to the control panel

3.1 Site selection
This instrument is intended to be used under the following environmental conditions
(IEC61010-1): Overvoltage category
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• Few mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85%RH
• No large capacity electromagnetic switches or cables through which large current is flowing
• No water, oil or chemicals or where the vapors of these substances can come into direct
contact with the controller
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
(20A), 4: Available (50A)
(Heater burnout alarm is not available for the DC current output)
(e.g.)
Supply voltage: 100 to 240V AC
Multi-input
Relay contact output
A1 output
Heating/Cooling control is not added.
Heater burnout alarm is not added.
Serial communcation is applied.
(1) PV display: Indicates the PV (input value) with a red LED.
(4)
(2) SV display: Indicates the SV (main set value) with a green LED.
(3) SV1 indicator: The green LED lights when SV is indicated
(5)
(6)
(4) OUT1 indicator: When OUT1 or heating output is ON, a
(7)
(8)
(5) OUT2 indicator: When OUT2 is ON, a yellow LED lights.
(9)
(6) A1 indicator: When A1 output is ON, a red LED lights.
(7) EVT indicator: When Event output (A2 output, Heater
(8) AT indicator: While auto-tuning or auto-reset is being
(9) TX/RX indicator: The yellow LED flashes while serial
: Selects the setting mode or registers the set value.
(By pressing the Mode key, the set value can be registered)
control output OFF function works.
(To cancel the function, press the OUT/OFF key again for approx. 1 second.)
, Pollution degree 2
communication is applied.)
on the SV display.
green LED lights. (For DC current output type, it flashes
corresponding to the MV (manipulated variable) in 0.25
second cycles.
burn out alarm output) is ON, a red LED lights.
performed, the yellow LED flashes.
communication is performing.
(32 to 122 )