Excitation
Current
4-Wire EX
RTD+
Filtered
ADC
Amplifier
3-wire & 4-wire
RTD–
Detection &
Compensation
COM
NI 9217
Figure 3. Input Circuitry for One Channel of the NI 9217 in 4-Wire Mode
Each channel has one terminal, RTD+, to which you connect the
positive lead of the RTD signal and one terminal, RTD–, to which
you connect the negative lead of the RTD signal. Each channel also
has a common terminal, COM, and an excitation current source
terminal, EX. You must connect the COM terminal to RTD–. All
four COM terminals are internally connected to the isolated ground
reference of the module. If you are using shielded wiring, connect
one end of the shield to the COM terminal. Refer to Figure 4 for an
illustration of how to connect an RTD to the NI 9217.