SPECIFICATIONS
Electrical
Installation must comply with all applicable electrical codes.
Locate the electrical supply flush with the back wall and
within the shaded area shown in the illustrations on the
following pages. For ease of installation, the electrical
supply for the oven can be placed in an adjacent cabinet
within reach of the conduit.
Performance may be compromised if the electrical supply is
less than 240 volts.
The oven is supplied with a conduit consisting of two
insulated hot lead conductors and a bare ground conductor.
The wiring diagram covering the control circuit is provided
with the oven.
RATING
PLATE
Rating plate location.
ELECTRICAL REQUIREMENTS
SINGLE OVEN
Electrical Supply
Service
Conduit
Total Amps
Max Connected Load
Min Supply Wire
DOUBLE OVEN
Electrical Supply
Service
Conduit
Total Amps
Max Connected Load
Min Supply Wire
grounded, 240/208 VAC, 60 Hz
30 amp dedicated circuit
4'
(1.2 m)
22
5.4 kW
L1, L2, ground—10 AWG
grounded, 240/208 VAC, 60 Hz
50 amp dedicated circuit
5'
(1.5 m)
45
10.8 kW
L1, L2, ground—8 AWG
|
wolfappliance.com
5