Boiler Error; Boiler Fault - Westinghouse WBCETNG750 Manual

Start-up maintenance parts warranty high mass condensing commercial boilers
Table of Contents

Advertisement

52
may show an error message and error code. This message and
code may be the result of a temporary condition, in which case
the display will revert to its normal readout when the condition
is corrected, or it may be a condition that the controller has
evaluated as not safe to restart the boiler. In this case, the boiler
control will be locked out, the red FAULT light will be lit, and the
message "LOCKOUT" will be displayed on the readout in the
lower line.
The boiler will not start until a qualified technician has repaired
the boiler and pressed the RESET button for more than 1 second.
If there is an error message displayed on the readout, and the
message "LOCKOUT" is not displayed and the FAULT light is not
lit, then the message is the result of a temporary condition and
will disappear when the problem corrects itself.
IMPORTANT NOTE: If you see error messages on your display
readout, call a technician immediately, since the message may
indicate a more serious problem will occur soon.
B. Boiler Error
The controller will display an error code and message when
an error condition occurs. These error codes, descriptions, and
recommended corrective actions are described in Section D.
C. Boiler Fault
1. The controller will illuminate the red "FAULT" indication light
and display a fault code and message when a fault condition
occurs. The alarm output will also activate. Most fault conditions
cause the CH pump to run in an attempt to cool the boiler.
2. Note the displayed fault code and refer to Section D for an
explanation of the message along with several suggestions for
corrective actions.
3. Press RESET to clear the fault and resume operation. Be sure
to observe the operation of the unit for a period of time to assure
correct operation and no reoccurrence of fault message.
When servicing or replacing components that are in direct
contact with boiler water, be certain that:
• There is no pressure in the boiler. (Pull the release on the
relief valve. Do not depend on the pressure gauge reading.
• The boiler water is not hot.
• The electrical power is disconnected.
• The gas is shut off.
Failure to make these checks could result in substantial property
damage, serious personal injury, or death.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN
SUBMERGED IN WATER. Immediately call a qualified service
technician. The appliance MUST BE replaced if it has been
submerged. Attempting to operate an appliance that has been
submerged could create numerous harmful conditions, such as
a potential gas leakage causing a fire and/or explosion, or the
release of mold, bacteria, or other harmful particulates into the
air. Operating a previously submerged appliance could result in
property damage, severe personal injury, or death.
NOTE: Appliance damage due to flood or submersion is
considered an Act of God, and IS NOT covered under product
warranty.
WHL-038 Rev. 1.29.16
If overheating occurs or the gas supply fails to shut off, do not
turn off electrical power to the circulating pump. This may
aggravate the problem and increase the likelihood of boiler
damage. Instead, shut off the gas supply to the boiler at the
gas service valve. Failure to do so may result in property
damage, personal injury, or death.
Label all wires prior to disconnecting them when servicing
the boiler. Wiring errors can cause improper and dangerous
operation. Failure to follow these instructions may result in
property damage or personal injury.
NOTE: If system return temperatures are maintained below
the dew point, condensation will form on the boiler cabinet
and cause some components to rust.