Venting; Approved Venting; Horizontal Vent System Clearances; Horizontal Terminations - kozy heat 56150 LAKEFIELD Installation And Operation Manual

Hide thumbs Also See for 56150 LAKEFIELD:
Table of Contents

Advertisement

IMPORTANT: Consult local and national installation codes to assure adequate combustion and ventilation air is available.
IMPORTANT: Flame height and appearance will vary depending upon venting configuration and type of fuel used.
IMPORTANT: Models #56150 & #56520 are manufactured with appropriate adaptor for proper connection to chosen approved venting.
NOTE: Page 15 has information on restrictor installation in conjunction with venting installation. Page 27 has information on restrictor recommendations depending
on burner flame appearance and instructions on installation after venting is completed.
CAUTION: This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
Refer to vent systems manufacturer's installation manual for complete installation instructions.
Installation must conform with venting requirements and restrictions as outlined in this manual.

APPROVED VENTING

Simpson Dura-Vent DV-GS 4" x 6-5/8" direct vent system (horizontal and vertical terminations).
Selkirk Metalbestos Chimney System 4" x 6-5/8" (horizontal and vertical terminations).
Security Chimney System 4" x 6-5/8" (horizontal and vertical terminations).
ICC Chimney System: 4" x 6-5/8" (horizontal and vertical terminations).
RLH Chimney System: 4" x 6-5/8" (horizontal and vertical terminations).
Amerivent / American metal Chimney System: 4" x 6-5/8" (horizontal and vertical terminations).
Metal Fab Chimney System: 4" x 6-5/8" (horizontal and vertical terminations).
This fireplace is designed to be used with rigid pipe only.

HORIZONTAL VENT SYSTEM CLEARANCES

TOP
1 inch (25 mm)

HORIZONTAL TERMINATIONS

MINIMUM: 3 ft. (914 mm) vertical + 90-degree elbow + 6 in. (152 mm) horizontal + termination cap.
MAXIMUM: 3 ft. (914 mm) vertical + 90-degree elbow + 21 ft. (6.40 m) horizontal + termination cap.
NOTE: Horizontal sections require 1/4" (6 mm) rise for every 12" (305 mm) of travel.

VERTICAL VENT SYSTEM CLEARANCES

TOP
1 inch (25 mm)

VERTICAL TERMINATIONS

MINIMUM: 3 ft. (914 mm) horizontal + termination cap.
MAXIMUM: 40 ft. (12.19 m) horizontal + termination cap.

VENTING

BOTTOM
1 inch (25 mm)
BOTTOM
1 inch (25 mm)
PAGE 14
SIDES
1 inch (25 mm)
SIDES
1 inch (25 mm)