Electronic Expansion Valve Open Error - Samsung DVM Series Service Manual

System air conditioner
Hide thumbs Also See for DVM Series:
Table of Contents

Advertisement

8
Troubleshooting

8-2-27. Electronic expansion valve open error

Outdoor unit display
Indoor unit display
Judgment method
Causes
1. Judgment method
Compressor is on in cooling operation & inlet/outlet temperature of stopped indoor unit is
below 0°C for 2.5 minutes.
2. Judgment time
Starts detecting after 5 minutes from completion of the safety start.
3. Control
Compressor
on
0 step
EEV(Wrong)
EEV(Normal)
4. Check method
1) Check whether the electronic expansion valve wire is connected correctly to the indoor unit PCB.
2) Open the electronic expansion valve kit to check whether the electronic expansion valve coil is correctly inserted.
3) Press the reset key (K3) of outdoor unit to check whether the same error appears.
1)
- If it is the close error, operate the related indoor unit.
1)
- If it is open error, put the related power off to check.
4) If there is no trouble for the above check items, replace the electronic expansion valve.
1)
- Since the replacement of electronic expansion valve is the inconvenient work to recover the all refrigerant in the system,
be sure to check the above items before replacing it.
x
(Open error of xth electronic expansion valve)
(Operation)
(Timer)
- Refer to the following judgment method
- Indoor unit electronic expansion valve open error
3 minutes
off
90 sec.
40 sec.
512 close
480 open
Normal control according to the compressor
- 194 -
(Fan)
(Filter)
(Removing frost)
safety start
capacity control
0 step