Technical Data; Specifications - Rinnai CHS199100 Installation And Operation Manual

Commercial hybrid system
Table of Contents

Advertisement

Specifications

Product Number
Minimum Gas Consumption Btu/h (kW/h)
Maximum Gas Consumption Btu/h (kW/h)
Tank Volume
Thermal Efficiency (C199i)
First Hour Delivery
Temperature Setting
Product Weight
Noise level
System Electrical Data
By-Pass Control
Gas Supply Pressure
Type of Appliance
Connections
Ignition System
Electric Connections
Water Temperature Control
Maximum Water Supply Pressure
Commercial Energy Star Certified (C199i)
Complies with South Coast Air Quality Management District
14 ng/J or 20 ppm NOx emission levels (C199i)
Type
Input
Product
of
Number
Gas
BTU/HR kW
NAT/
CHS199100
199,000
LP
* First Hour Delivery Rating is a theoretical calculation based on 70% usable tank capacity (tank Capacity x .70 + (recovery) = First
Hour Rating
Our products are continually being updated and improved; therefore, specifications are subject to change without prior notice.
The maximum inlet gas pressure must not exceed the value specified by the manufacturer. The minimum value listed is for the
purpose of input adjustment.

Technical Data

Normal
Standby
Anti-frost Protection
Max Current
Fuse
Natural Gas
Propane
Thermal
°F
Tank
Efficiency
Capacity
°C
119 U.S.
GPH
Gals.
58
96%
450
LPH 2922 2192 1753 1461 1253 1093 973
Liters
Commercial Hybrid System
Tankless Engine - 10 A, Controller - 10 A
Condensing Hybrid System: Condensing tankless, Insulated Storage Tank,
Integrated Temperature Controller: DC 12 Volts (Digital)
Simulation Feed forward and Feedback
RECOVERY CAPACITIES
U.S. GALLON/HR LITERS/HR AT TEMPERATURE RISE INDICATED
30°F
40°F
50°F
60°F 70°F 80°F 90°
17°C 22°C 28°C
33°C 39°C 44°C 50°C 56°C
772
579
463
386
331
CHS199100
15,200 (4.5)
199,000 (58.3)
119 Gallons
(450 Liters)
96%
315 Gallons
(1192 Liters)
98° F (37° C) to 185° F (85° C)
428 lb (194 kg)
52 dB
256 W
44 W
326 W
5.5 A
Electronic
4.0 - 10.5 inch W.C.
8.0 - 13.5 inch W.C.
Pump & Control
Gas Supply Inlet - 3/4" MNPT
Hot Water Outlet - 2" MNPT
Cold Water Inlet - 2" MNPT
Direct Electronic Ignition
Appliance: AC 120 Volts, 60Hz.
150 PSI
Yes
Yes
100°F 110°F
61°C
289
257
232
211
878
799
120°F 130°F 140°F
67°C
72°C
78°C
193
178
165
731
673
625
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents