Vision SPIRIT II G User Manual

True online double conversion ups

Advertisement

User Manual

Vision Spirit II G
6-10KVA
PF0.9 – 1/1 phase
True online double conversion UPS

Advertisement

Table of Contents
loading

Summary of Contents for Vision SPIRIT II G

  • Page 1: User Manual

    User Manual Vision Spirit II G 6-10KVA PF0.9 – 1/1 phase True online double conversion UPS...
  • Page 2 EMC and safety standards, The UPS has become standard product meets the world’s advanced level. Read this manual carefully before installation. This manual provides technical support to the operator of the equipment. - 2 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 3: Safety Instruction

    It is forbidden to pour liquid or put any objects into the UPS. Don’t use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended. - 3 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 4 11) Don’t open the battery, electrolyte inside will do harm to eyes and skin. Please use plenty of clean water to wash if touching and go to see a doctor - 4 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 5: Table Of Contents

    3.5 LCD operation menu ......................- 23 - 3.5.1 Main menu switching....................- 23 - 3.5.2 Submenu switching ...................... - 23 - 3.5.3 Priority of info displayed on LCD ................- 23 - - 5 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 6 Appendix 2. RS232 communication port definition ............. - 28 - Appendix 3. Specification ......................- 29 - Appendix 4. Option ........................- 31 - Appendix 5. UPS message table ....................- 31 - - 6 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 7: Production Introduction

    External battery External battery battery battery 1.3 System principle diagram The system can work in single unit, and parallel so as to enhance the reliability. Fig.1-1 Single unit - 7 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 8: Features

     Maintenance bypass switch is provided so the power supply to load will not be interrupted during repair  Friendly maintenance module design, easy for maintenance. 1.5 Product overview 1.5.1 Product view F1-2 Complete unit view - 8 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 9: Lcd Operation Instruction

    Fig.1-3 LCD control panel introduction LCD Display Board Output Indicator Inverter Indicator Off button Battery Indicator On button Mains (AC) Indicator right or down Bypass Indicator Enter/Save Fault Indicator left or up - 9 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
  • Page 10  Battery capacity setting includes the Ah of each battery unit, battery quantity 16 to 20, parallel group number  Parallel setting  UPS ID setting  UPS amount setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 9 -...
  • Page 11 Battery float charging Battery Charging Battery Boost charging Battery Boost Inverter on/off Inverter ON/ Inverter OFF Master of UPS Inver Master Maintenance switch close or open SWMB ON/ SWMB OFF SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 10 -...
  • Page 12: Display Instruction

    AC input/output, inverter, battery, BUS, parallel, temperature. See Fig 4 to 12 below. FIGURE FIGURE FIGURE Mains Output Output 220.0V 50.0Hz 220.0V 0.0A 0KVA 50.0Hz Load: 0% Fig.4:MAIN INPUT INFO Fig.5:OUTPUT INFO Fig.6:OUTPUT INFO SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 11 -...
  • Page 13 See Fig 15 to 19 SETTING SETTING Mode: V-Level:220V Batt num:16 F-Level:50Hz Batt cap:7AH Fig.15:setting menu Fig.16:setting menu SETTING SETTING V-upper Buzzer:Enable V-lower -45% Fig.17:setting menu Fig.18:setting menu SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 12 -...
  • Page 14: Rear Panel Instruction

    P-amount P-Redund Fig.19:Parallel setting 1.5.4 Rear panel instruction 1.5.4.1 6k H/S rear panel Fig.1-4 Rear Instruction Parallel slot Maintenance bypass switch (covered) Intelligent slot Input switch Input/output/battery terminal(covered) SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 13 -...
  • Page 15 1.5.4.2 10k H/S rear panel Parallel slot Maintenance bypass switch (covered) Intelligent slot Input switch Input/output/battery terminal(covered) SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 14 -...
  • Page 16: Installation

    UPS. Please contact dealer if other types of loads is required to be connected with. * For the sake of user and equipments, please betake correct power configuration. Fig.2-1 Correct power configuration SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 15 -...
  • Page 17: Installation

    CAUTION It is recommended to connect or replace battery after switching off the system; don’t reverse battery polarity when doing battery hot-swapping. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 16 -...
  • Page 18 B. Insert the SNMP card and tighten the screws C. Connect the UPS with internet by network cable. D. Refer to the SNMP manual provided to do SNMP setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 17 -...
  • Page 19: Connection Of Parallel System

    UPS in parallel should be N* 10AWG or 8AWG (N refers to the number of the UPS in parallel.) Make sure the cables are as shorter as possible to reduce any possible noise interference to data transfer. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 18 -...
  • Page 20: Operation

    Charge batteries for at least 8 hours when the UPS is used at the first time as battery has self-discharge characteristics even though the UPS has been fully charged by manufacturer before shipping. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 19 -...
  • Page 21: Eco Mode

    Gradually increase the load after the UPS working normally. Load information can be checked through the LCD. If the buzzer beeps twice per second and overload alarm is displayed on LCD, it SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 20 -...
  • Page 22: Inverter Shutdown

    When the inverter is defective or over temperature inside UPS, UPS will transfer to bypass mode if the bypass is normal. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 21 -...
  • Page 23: Transfer To Bypass If Overload

    10mins, UPS will shut down automatically or press the off button to shut down in after 10s. Before restarting the UPS, please make sure that the short circuit problem has been solved. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 22 -...
  • Page 24: Ups Monitoring

    LCD if no further operation on buttons. If LCD is not displaying the submenu of running parameters, it will return to main menu if 30s as long as there isn’t any operation on buttons. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 23 -...
  • Page 25: Maintenance

    1) Don't short circuit battery, or it may cause a fire. 2) Don’t open battery, released electrolyte is harmful to skin and eyes 4.3 Visual checking Keep ventilation of the UPS in good condition. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 24 -...
  • Page 26: Ups Status Checking

    Pay attention to the backup time if AC indicator blinking A range UPS is in battery mode Buzzer beeps twice every second, LCD UPS overload Disconnect some loads shows “output overload” SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 25 -...
  • Page 27 “output fault” Abnormal sound or shut down the UPS immediately Fault inside UPS smell and Contact distributor Please provide the UPS model, SN when calling distributor for maintenance. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 26 -...
  • Page 28: Appendix 1. Usb Communication

    Pin 3 D+, Pin 4 GND Available function of USB ■ Monitor UPS power status ■ Monitor UPS alarm info ■ Monitor UPS running parameters ■ Timing off/on setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 27 -...
  • Page 29: Appendix 2. Rs232 Communication Port Definition

    ◆ Monitor UPS running parameters. ◆ Timing off/on setting. RS-232 communication data format: Baud rate ---------- 2400bps Byte length ---------- 8bit End bit ---------- 1bit Parity check --------none SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 28 -...
  • Page 30: Appendix 3. Specification

    Frequency precision ±0.1% Rating Frequency 50Hz/60Hz Frequency track speed 1Hz/s 105%~110%,1Hr 110%~125% 10min Overload 125%~150% 1min ≥150% 200ms Overload for bypass 125% Peak value factor ≥90% Efficiency at normal SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 29 -...
  • Page 31 Meeting IEC60664-1 1.2/50uS+8/20uS 6kV/3kA. Protection IP20 Parallel circumfluence 1+1≤8%,N+1≤3% Parallel equal current 1+1≤8%,N+1≤10% Dimension & weight DIMENSION Capacity 6KVA/5.4KW 10KVA/9KW Height Width Depth 6KVA:62Kg(S)/23(H) Net weight 10KVA:64Kg(S)/25(H) Color Blackness SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 30 -...
  • Page 32: Appendix 4. Option

    Beep continuously Fault LED lit Inverter Thyristor broken Beep continuously Fault LED lit Bypass Thyristor short Beep continuously Fault LED lit Bypass Thyristor broken Beep continuously Fault LED lit SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 31 -...
  • Page 33 Mains freq. abnormal Once per 2 seconds BATTERY LED lit Bypass Not Available BPS blinking Bypass unable to trace BPS blinking Inverter on invalid ▪ ▪ ▪ ▪ ▪ SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 32 -...