User Manual Vision Spirit II G 6-10KVA PF0.9 – 1/1 phase True online double conversion UPS...
Page 2
EMC and safety standards, The UPS has become standard product meets the world’s advanced level. Read this manual carefully before installation. This manual provides technical support to the operator of the equipment. - 2 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
It is forbidden to pour liquid or put any objects into the UPS. Don’t use liquid extinguisher if there is a fire, a dry powder extinguisher is recommended. - 3 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
Page 4
11) Don’t open the battery, electrolyte inside will do harm to eyes and skin. Please use plenty of clean water to wash if touching and go to see a doctor - 4 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
External battery External battery battery battery 1.3 System principle diagram The system can work in single unit, and parallel so as to enhance the reliability. Fig.1-1 Single unit - 7 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
Maintenance bypass switch is provided so the power supply to load will not be interrupted during repair Friendly maintenance module design, easy for maintenance. 1.5 Product overview 1.5.1 Product view F1-2 Complete unit view - 8 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
Fig.1-3 LCD control panel introduction LCD Display Board Output Indicator Inverter Indicator Off button Battery Indicator On button Mains (AC) Indicator right or down Bypass Indicator Enter/Save Fault Indicator left or up - 9 - SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com...
Page 10
Battery capacity setting includes the Ah of each battery unit, battery quantity 16 to 20, parallel group number Parallel setting UPS ID setting UPS amount setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 9 -...
Page 11
Battery float charging Battery Charging Battery Boost charging Battery Boost Inverter on/off Inverter ON/ Inverter OFF Master of UPS Inver Master Maintenance switch close or open SWMB ON/ SWMB OFF SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 10 -...
UPS. Please contact dealer if other types of loads is required to be connected with. * For the sake of user and equipments, please betake correct power configuration. Fig.2-1 Correct power configuration SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 15 -...
CAUTION It is recommended to connect or replace battery after switching off the system; don’t reverse battery polarity when doing battery hot-swapping. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 16 -...
Page 18
B. Insert the SNMP card and tighten the screws C. Connect the UPS with internet by network cable. D. Refer to the SNMP manual provided to do SNMP setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 17 -...
UPS in parallel should be N* 10AWG or 8AWG (N refers to the number of the UPS in parallel.) Make sure the cables are as shorter as possible to reduce any possible noise interference to data transfer. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 18 -...
Charge batteries for at least 8 hours when the UPS is used at the first time as battery has self-discharge characteristics even though the UPS has been fully charged by manufacturer before shipping. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 19 -...
Gradually increase the load after the UPS working normally. Load information can be checked through the LCD. If the buzzer beeps twice per second and overload alarm is displayed on LCD, it SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 20 -...
When the inverter is defective or over temperature inside UPS, UPS will transfer to bypass mode if the bypass is normal. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 21 -...
10mins, UPS will shut down automatically or press the off button to shut down in after 10s. Before restarting the UPS, please make sure that the short circuit problem has been solved. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 22 -...
LCD if no further operation on buttons. If LCD is not displaying the submenu of running parameters, it will return to main menu if 30s as long as there isn’t any operation on buttons. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 23 -...
1) Don't short circuit battery, or it may cause a fire. 2) Don’t open battery, released electrolyte is harmful to skin and eyes 4.3 Visual checking Keep ventilation of the UPS in good condition. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 24 -...
Pay attention to the backup time if AC indicator blinking A range UPS is in battery mode Buzzer beeps twice every second, LCD UPS overload Disconnect some loads shows “output overload” SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 25 -...
Page 27
“output fault” Abnormal sound or shut down the UPS immediately Fault inside UPS smell and Contact distributor Please provide the UPS model, SN when calling distributor for maintenance. SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 26 -...
Pin 3 D+, Pin 4 GND Available function of USB ■ Monitor UPS power status ■ Monitor UPS alarm info ■ Monitor UPS running parameters ■ Timing off/on setting SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 27 -...
Frequency precision ±0.1% Rating Frequency 50Hz/60Hz Frequency track speed 1Hz/s 105%~110%,1Hr 110%~125% 10min Overload 125%~150% 1min ≥150% 200ms Overload for bypass 125% Peak value factor ≥90% Efficiency at normal SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 29 -...
Page 31
Meeting IEC60664-1 1.2/50uS+8/20uS 6kV/3kA. Protection IP20 Parallel circumfluence 1+1≤8%,N+1≤3% Parallel equal current 1+1≤8%,N+1≤10% Dimension & weight DIMENSION Capacity 6KVA/5.4KW 10KVA/9KW Height Width Depth 6KVA:62Kg(S)/23(H) Net weight 10KVA:64Kg(S)/25(H) Color Blackness SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 30 -...
Beep continuously Fault LED lit Inverter Thyristor broken Beep continuously Fault LED lit Bypass Thyristor short Beep continuously Fault LED lit Bypass Thyristor broken Beep continuously Fault LED lit SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 31 -...
Page 33
Mains freq. abnormal Once per 2 seconds BATTERY LED lit Bypass Not Available BPS blinking Bypass unable to trace BPS blinking Inverter on invalid ▪ ▪ ▪ ▪ ▪ SPIRIT II G 6-10KVA PF0.9 LCD - UPS www.visionups.com - 32 -...