CI-24 – Installation
Specifications subject to change without notice. | 86-0468-00r3 9/99 | USA 150729 | Page 4 of 8

SENSOR ADJUSTMENT

The sensor comes factory preset and ready for operation.
If testing of operation is desired:
Remove the sensor's cover (twist).
Refer to the DIP switch settings chart below for switch configurations.
Make sure that office furniture and fixtures are in place.
1. Confirm the Override DIP switch is set to Normal (DIP switch #4 to OFF)
2. Restore power and turn on the system interfacing with the Isolated Relay.
• There is a one minute warm-up when power is initially restored to the
sensor before the sensor works properly.
3. Set Time Delay to minimum: DIP switches #1 and 2 to ON (30 seconds).
4. Set Sensitivity to maximum: DIP switch #3 to ON.
5. Replace the sensor's cover.
6. Move away from sensor and be still. The sensor should time-out after
30 seconds and the isolated relay contacts should return to their "normal"
condition (Normally Open or Closed), see Wiring Directions diagram.
Note: If the sensor does not time-out or the isolated relay does not return to
its normal condition, move farther away or out of sight of the sensor, or see
Unwanted Sensor Activations under Troubleshooting.
7. Reset the Time Delay to the desired delay (DIP switches #1 and 2).

DIP SWITCH SETTINGS

DIP Switch Control
for Time Delay,
Sensitivity, and
Override
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
1
2
ON
ON
1
2
3
4
LED
DIP Switch #
30 seconds
3
4
10 minutes
20 minutes
30 minutes
.
Sensitivity
Minimum
.
Maximum
.
Normal
Override
=ON
=Factory Presets
.
TROUBLESH
LED does not fla
1. Determine if th
2. Check that the
3. Check that the
4. Check that 24VA
Isolated relay not
1. Check that Tim
2. Check Sensitiv
3. Check that all
4. Using proper p
5. Check that 24VA
6. Use an ohmme
1 2 3 4
Unwanted senso
Possible causes
1. People moving
– =OFF
2. HVAC vents w
Possible solutions
1. Masking (see
2. Setting the Sen
3. Relocating the
Sensor Override:
If the sensor fails,
This overrides the
US
W
• If it is prese
(if available)
• Turn off the
- With moti
between
- With moti
between
• Turn Sensitiv
a cloth (not
- Check tha
- Check tha
of the sensor a