Wiring Directions - Intec CI-24 Installation Manual

360 pir occupancy sensor
Table of Contents

Advertisement

CI-24 – Installation
Specifications subject to change without notice. | 86-0468-00r3 9/99 | USA 150729 | Page 6 of 8
MASKING
An insert (mask) is supplied to allow elimination of coverage in unwanted areas.
The mask is cut as needed and mounted onto anchor pins in the sensor's cover.
IMPORTANT: Do not use the mask if full coverage is desired.
IMPORTANT: Before securing the sensor in the mounting location, the
assembled sensor must be turned so the unmasked portion of the lens
faces the coverage area (the blue masked area is visible through the lens).
IMPORTANT: For an already installed sensor—If the sensor can NOT be turned,
then the mask must be cut so that when installed it will be oriented correctly
(note the location of the securing pins in the cover and note that the cover
turns as it locks into position).
Note: At the edges of the masking, there is a small area of reduced sensitivity,
illustrated as the lighter area in the examples below.
Cut mask into sections
for desired coverage,
shown right.

WIRING DIRECTIONS

TURN POWER OFF AT CIRCUIT BREAKER BEFORE WIRING SENSOR
Connect 24VAC or +24VDC Supply to the RED and Return to the BLACK
wire from the sensor.
Isolated Relay: (Rated for 1A @24VDC or 24VAC)
Connect the wires necessary to the application that requires this output.
GREEN (Normally Closed)—Open when occupancy is detected
ORANGE (Common) (must be used for proper operation)
YELLOW (Normally Open)—Closed when occupancy is detected
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | relevantsolutions.com/inteccontrols
Mask
CAUTION
24VAC or +24VDC, ±10%
Isolated Relay Outputs
Normally Closed Contact
Common
Normally Open Contact
24VAC or 24VDC Return
Coverage area
Reduced sensitivity
Wires
RED
GREEN
ORANGE
YELLOW
BLACK
CI-24
Sensor