[ II Restrictions ]
(3) Size of the pipe that fits the sub BC controller ports
To Main BC controller
*1
Reducer
(Standard supplied parts)
Indoor
P18 model or below P24 - P54 models P72 - P96 models
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor
units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the P72 through P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use
an optional twinning pipe kit (Model: CMY-R160-J) to merge two ports before connecting them.
3) To connect multiple indoor units to a port (or to a junction pipe)
ŒMaximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)
ŒMaximum number of connectable indoor units: 3 units
ŒBranch joint: Use CMY-Y102S-G2 (optional accessory).
ŒRefrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units
P54 or below
P55 - P72
P73 - P96
Operation
On the BC controller
side
HWE0913A
Connection: Brazed connection
*2
Junction pipe kit
BC controller (sub)
(Model name:
CMY-R160-J)
(Optional accessory)
Indoor
Indoor
Liquid pipe
ø9.52 [3/8"]
ø9.52 [3/8"]
ø9.52 [3/8"]
Total capacity of the in-
door units that are con-
High-pressure side
nected to the BC
controller
ø15.88 [5/8"]
P72 model or below
(Brazed connection)
P73 - P108
ø19.05 [3/4"]
(Brazed connection)
P109 - P126
P127 - P144
(Brazed connection)
P145 - P168
- 57 -
Branch joint (Model name:CMY-Y102S-G2)
(Optional accessory)
A
B
Indoor
Indoor
3*
Maximum of 3 units per port
Total capacity of P54 or below
(All units connected to the same port
must be in the same operating mode.)
Pipe sections
Low-pressure side
(liquid)
(gas)
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
ø28.58 [1-1/8"]
ø22.2 [7/8"]
(Brazed connection)
Indoor
Unit : mm [inch]
Gas pipe
ø15.88 [5/8"]
ø19.05 [3/4"]
ø22.2 [7/8"]
Unit : mm [inch]
Liquid pipe side
ø9.52 [3/8"]
(Brazed connection)
ø12.7 [1/2"]
(Brazed connection)
ø15.88 [5/8"]
(Brazed connection)
GB