Mitsubishi Electric PURY-P72TYJMU-A Service Handbook page 196

Table of Contents

Advertisement

[ VIII Test Run Mode ]
(2) Heating only operation
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0913A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 187 -
Outdoor unit model
PURY-P168TSJMU-A
PURY-P96TJMU-A
CMB-P108NU-GA
21.1°C/í [70 °F/í]
8.3°C/6.1°C [47°F/43°F]
Unit
-
30/30/36/36/36
m
[ft]
-
kg
A
V
Hz
74
295/295/350/350/350
110/110/980
2.52/0.63
[365/91]
MPa
[psi]
78 [172]
0 [32]
-2 [28]
°C
-3 [27]
[°F]
-3 [27]
40 [104]
PURY-P72TJMU-A
5
5
5 [16-3/18"]
10 [32-3/4"]
55 [180-1/8"]
Hi
38.5 [85]
42.5
230
52
2.52/0.70
[365/102]
2.46/2.20
[357/319]
68 [154]
2 [36]
1 [34]
1 [34]
1 [34]
40 [104]
34 [93]
65 [149]
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents