Mitsubishi Electric PURY-P72TYJMU-A Service Handbook page 49

Table of Contents

Advertisement

[ II Restrictions ]
(5) Address setting method
Pro-
ce-
Unit or controller
dur
es
1
Indoor
Main unit IC
unit
Sub unit
2
LOSSNAY
3
MA
Main re-
mote
remote
controller
control-
ler
Sub re-
mote con-
troller
4
Outdoor unit
5
Auxilia-
BC
controller
ry out-
(Sub)
door
unit
BC con-
troller
(Main)
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0913A
Address
setting
range
ŒAssign the smallest address to the main unit in the
01 to 50
group.
ŒIn a system with a sub BC controller, make the set-
tings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC control-
ler
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that
the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of
the main unit in the same group +1. (Main unit address
+1, main unit address +2, main unit address +3, etc.)
LC
01 to 50
Assign an arbitrary but unique address to each of these
units after assigning an address to all indoor units.
MA
No set-
tings re-
quired.
MA
Sub re-
Settings to be made with the Sub/Main switch
mote
controller
ŒThe sum of the smallest address of the indoor units in
OC
51 to 100
the same system and 50.
OS
ŒAssign sequential address to the outdoor units in the
same refrigerant circuit.
ŒThe outdoor units are automatically designated as
OC and OS.(Note)
BS
51 to 100
Assign an address that equals the sum of the smallest
address of the indoor units that are connected to the
sub BC controller and 50.
BC
51 to
OC (or OS if it exists) +1
100
Setting method
-
- 40 -
Notes
ŒPort number setting is re-
quired
ŒTo perform a group opera-
tion of indoor units that
feature different functions,
designate the indoor unit
in the group with the
greatest number of func-
tions as the main unit.
None of these addresses may
overlap any of the indoor unit ad-
dresses.
Make the same indoor unit group
settings with the system controller
as the ones that were made with
the MA remote controller.
ŒTo set the address to 100, set
the rotary switches to 50.
ŒTo set the address to 100, set
the rotary switches to 50.
ŒIf the addresses that is assigned
to the main BC controller over-
laps any of the addresses that
are assigned to the outdoor
units or to the sub BC control-
ler, use a different, unused ad-
dress within the setting range.
ŒThe use of a sub BC controller
requires the connection of a
main BC controller.
Fac-
tory
set-
ting
00
00
Mai
n
00
00
GB