Example Connection With One Sub-Distribution - HomeMatic HMW-LGW-O-DR-GS-EU Installation And Operating Manual

Rs485 lan gateway
Hide thumbs Also See for HMW-LGW-O-DR-GS-EU:
Table of Contents

Advertisement

Available languages

Available languages

The shield only has to be connected on one
side. Although the shield can be connected on
any side, we recommend using the LAN gate-
way side.
To avoid short-circuits, make sure that the side
of the shield or continuity wire which is not
connected is made safe or cut back so that it
finishes with the cable insulation.
The wire routed in parallel with the shield (continuity
wire, see figure below) must be connected to the GND
socket of the HomeMatic wired device.
Jacket
Conductor
46
Shield
Drain wire
6.2 Example connection with one sub-dis-
tribution board
Main distribution
LAN Gateway
A
B
1.3
1.7
+24 V
GND
1.4
1.8
Drain wire
(connected)
Shielded cable
If there is more than one sub-distribution
board, you should make the shield connection
separately in each of them, i.e.:
• Incoming shielded cable
shield
• Outgoing shielded cable
nected to GND, etc.
Sub-distribution
Actuator
Prog.
+24 V
GND
A
B
1.4
1.8
1.3
1.7
Drain wire
(not connected)
Do not connect
Shield con-
47