3 Commissioning
Flow chart Quick Commissioning (Level 1 Only)
P0010 Start Quick Commissioning
0
Ready to Run
1
Quick Commissioning
30 Factory Setting
Note
P0010 must always be set back to '0' before
operating the motor. However if P3900 = 1 is set
after commissioning this is done automatically.
P0100 Operation for Europe/N. America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in kW; f default 60 Hz
Note
Settings 0 & 1 should be changed using the DIP
switches to allow permanent setting.
P0304 Rated Motor Voltage 1)
10 V - 2000 V
Nominal motor voltage (V) from rating plate
P0305 Rated Motor Current 1)
0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power 1)
0 kW - 2000 kW
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequency 1)
12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate
P0311 Rated Motor Speed 1)
0 - 40000 1/min
Nominal motor speed (rpm) from rating plate
1) Motor-specific parameters – see motor rating plate.
2) The parameters offer more setting options than listed here. See Parameter List for further setting
options.
44
P0700 Selection of Command Source 2)
(on / off / reverse)
0
Factory Setting
1
Basic Operator Panel
2
Terminal / Digital Inputs
P1000 Selection of Frequency Setpoint 2)
0
No frequency setpoint
BOP frequency control ↑↓
1
2
Analogue Setpoint
P1080 Min. Motor Frequency
Sets minimum motor frequency (0-650Hz) at which
the motor will run irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1082 Max. Motor Frequency
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1120 Ramp-Up Time
0 s - 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
P1121 Ramp-Down Time
0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P3900 End Quick Commissioning
0
End Quick Commissioning without motor
calculation or factory reset.
1
End Quick Commissioning with motor
calculation and factory reset (Recommended)
2
End Quick Commissioning with motor
calculation and with I/O reset.
3
End Quick Commissioning with motor
calculation but without I/O reset.
MICROMASTER 440
Issue A2
Operating Instructions
6SE6400-5AC00-0BP0