Fujitsu AU*A30LBLU Design & Technical Manual page 35

Table of Contents

Advertisement

Setting the Outlet Directions
• Select the setting values in the table below for using a 3-way
outlet. (The unit is factory-set to "00".)
Setting Description
Function Number
4-way
3-way
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to
clean the filter.
• Select the time setting for the filter sign display interval in the
table below according to the amount of dust or debris in the
room. (The unit is factory-set to "00".)
• If you do not wish the filter sign to be displayed, select the setting
value for "No indication".
Setting Description
Function Number
Standard
(2,500 hours)
Long interval
(4,400 hours)
Short interval
(1,250 hours)
No indication
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be selected
as shown in the table below. (The unit is factory-set to "00".)
Setting Description
Function Number
Standard
Lower control
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be changed
as shown in the table below. (The unit is factoryset to "00".)
Setting Description
Function Numbe
Standard
Lower control
Slightly warmer control
Warmer control
Setting Other Functions
• The following settings are also possible, depending on the
operating conditions. (The unit is factory-set to "00".)
Auto Restart
Setting Description
Function Number
Yes
No
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description
Function Number
No
Yes
• If setting value is "00", room temperature is controlled by the
indoor unit temperature sensor.
• If setting value is "01", room temperature is controlled by either
indoor unit temperature sensor or remote control unit sensor.
Setting Value
00
22
01
Setting Value
00
01
11
02
03
Setting Value
00
30
01
Setting Value
00
01
31
02
03
Setting Value
00
40
01
Setting Value
00
42
01
- (01 - 32) -
Setting record
• Record any changes to the settings in the following table.
Setting
Ceiling height
Vertical direction adjusting
scope
Outlet directions
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
3. Setting the room temperature detection
location
The detection location of the room temperature can be selected
from the following two examples. Choose the detection location
that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature
sensor.
(1) When the THERMO SENSOR button is pressed, the lock
display flashes because the function is locked at the factory.
B. Indoor unit/remote controller setting (room
temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller
can be used to detect the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION
SETTING, which will be described later.
(2) Press the THERMO SENSOR button for 5 seconds or more to
select the temperature sensor of the indoor unit or the remote
controller.
NOTE
If the function to change the temperature sensor is used as
shown in examples A (other than example B), be sure to lock the
detection location.
If the function is locked, the lock display
THERMO SENSOR button is pressed.
Setting Value
A
Indoor unit
B
Indoor unit
will flash when the