Fujitsu AU*A30LBLU Design & Technical Manual page 24

Table of Contents

Advertisement

PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT
zConnect the air outlet duct at up to two locations among the four duct
connection locations. (Do not connect ducts at three or more locations.)
D
C
zBlow-off pattern when a branch duct is installed
Bi-directional branching, main unit bi-directional branching
Close
Branch
zOnce the location where the duct is to be connected is decided,
always be sure to close the outlets in the same direction.
A
B
Close
Branch
DUCT (Locally procured parts)
Close the outlet here.
* Use only after closing the outlet of the cassette on the
side on which the duct is used, using the "Air outlet
shutter plate (UTR-YDZC)".
- (01 - 21) -
Branch
Close
Close
Branch

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ao*a30lftlAo*a36lbtlAo*a36lftlAu*a36lbluAo*a30lbtl

Table of Contents