Point Of Remote Controller Installation; Remote Controller Installation - LG MFL62541004 Installation Manual

Table of Contents

Advertisement

REMOTE CONTROLLER INSTALLATION

22
REMOTE CONTROLLER INSTALLATION
Point of remote controller in-
stallation
- Although the room temperature sensor is in
the indoor unit, the remote control box
should be installed in such places away from
direct sunlight and high humidity.
Installation of the remote control
box
- Select places that is not splashed by water.
- Select control position after receiving cus-
tomer approval.
- The room temperature sensor of the thermo-
stat for temperature control is built in the in-
door unit.
- This remote controller equipped with liquid
crystal display. If this position is higher or
lower, display is difficult to see.
(The standard height is 1.5m high)
Routing of the remote control cord
- Keep the remote control cord away from the
refrigerant piping and the drain piping.
- To protect the remote control cord from elec-
trical noise, place the cord at least 5cm away
from other power cables. (Audio equipment,
Television set, etc)
- If the remote control cord is secured to a
wall, provide a trap at the top of the cord to
prevent water droplets from running.
Electrical wiring to the indoor unit
Remote controller
CN REMO
The maximum length of the
cord is 100m. If the length of
the cord exceeds 50m, use a
wire size greater than 0.5mm
Make sure that wire and
terminal numbers are
matched on unit side
CN REMO
and remote controller
side.
Main board
Put the installation paper on the place and de-
termine the position and height of the fixing
screws of the deluxe wired remote controller.
- Refer to the printed side of the installation
paper.
Wall
Installation paper
The position of the fixing screws
Remove the installation paper before installing
the remote controller so that it can fit into the
right place.
Fixing the
remote controller
- When installing the deluxe wired remote
controller, do not install it so that it is buried
to the wall.
(This can cause error in the temperature sen-
sor)
- When installing multiple deluxe wired re-
mote controllers horizontally in one location,
leave a minimum distance apart (20mm).
(This can cause error in the temperature sen-
sor)
- Do not install the cable with a distance of 50
m or longer. (This can cause communication
error.)
- When installing the cable, check whether the
connector between the remote controller
2
.
and the product is installed properly. The
connector will not be connected when in-
stalled in opposite sides.
Fixing the
connecting cable

Advertisement

Table of Contents
loading

Table of Contents