Insulation, others

Insulate the joint and tubes completely.
Thermal insulation : All thermal insulation
must comply with local requirement.
Indoor unit
Union for
liquid pipe
Thermal insulator for refrigerant pipe
(Local supply) Thermal insulator for
Overlap with thermal
insulator for piping.
Hose crip for thermal insulator(Local supply)
Make sure that there is no clearance here.
Refrigerant pipe
- Insulate and tape the gas piping.
Power cable
Liquid pipe
Thermal insulator
CAUTION
!
Cutting line of insulation must look upper
direction. Thickness of insulation is
10mm or over.
NOTE
!
Recommended Insulation material
Meterial : FOAM PE
Thickness : 10mm
Density : less than 0.032 ±0.005(g/cm
Thermal conductivity : less than
0.03(kcal/m.hr.°C)
Refrigerant pipe
and thermal
insulator
(Local supply)
Hose crip for
thermal insulator
(Local supply)
Thermal insulator
for refrigerant pipe
(Local supply)
Union for gas pipe
piping(Local supply)
Tape
Gas pipe
2
)
THE INDOOR UNIT INSTALLATION
Test and check
* After all workings are finished, check the
working and operation.
- Air distribution : Is the air circulation good?
- Drain : Is the drainage smoothly and no
sweating?
- Gas leakage : Is the piping connection cor-
rectly?
- Wiring : Is the wiring connection correctly?
- Lock-bolt : Is the lock-bolt of compressor
loosened?

Checking the Drainage

Checking the Drainage
* Check the drainage.
- Spray one or two glasses of water upon the
evaporator.
- Ensure that water flows drain hose of indoor
unit without any leakage.
11