Placement And Installation; Piping And Fittings Specifications - Lennox EL296UH045XE36B Unit Information

El296uhe series
Hide thumbs Also See for EL296UH045XE36B:
Table of Contents

Advertisement

II-PLACEMENT AND INSTALLATION
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri­
can Society for Testing and Materials (ANSI/ASTM) stan­
dards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad­
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica­
tion, or separation that cannot be removed by stirring. Re­
fer to the table 14 below for approved piping and fitting ma­
terials.
CAUTION
Solvent cements for plastic pipe are flammable liq­
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of ce­
ment with skin and eyes.
TABLE 14

PIPING AND FITTINGS SPECIFICATIONS

Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
Schedule 40 CPVC (Pipe)
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
Schedule 40 ABS (Pipe)
Schedule 40 ABS (Fittings)
ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings)
PVC-DWV (Drain Waste & Vent)
Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro by Duravent
EL296UHE exhaust and intake connections are
made of PVC. Use PVC primer and solvent cement
when using PVC vent pipe. When using ABS vent
pipe, use transitional solvent cement to make con­
nections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent ce­
ment meeting ASTM specifications, refer to Table 14. As
an alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using fittings and pipe made of the same
materials. Use transition solvent cement when bonding
ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean in­
side socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only - Pipe, fittings, primer and
solvent cement used to vent (exhaust) this appliance must
be certified to ULC S636 and supplied by a single
manufacturer as part of an approved vent (exhaust) sys­
D1785
tem. In addition, the first three feet of vent pipe from the fur­
F891
nace flue collar must be accessible for inspection.
D2466
F441
F438
D2241
F442
F628
D1527
D2468
D2661
D2665
ASTM
SPECIFICATION
F656
D2564
F493
D2235
D2564, D2235, F493
D3138
MARKING
ULCS636
ULC-S636
Page 22