Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
Number of blinks/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
received)
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Note: The supported check codes may vary depending on the connected outdoor unit.
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
OCH616
Beep
Beep
Beep
1 st
2 nd
3 rd
On
On
On
0.5 s
0.5 s
0.5 s
Beep
1 st
On
On
Approx. 3 s
0.5 s
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (liquid or 2-phase pipe) sensor error
E6, E7
Indoor/indoor unit communication error
P4
Drain sensor error / Float switch connector open
P5
Drain overflow protection operation
PA
Forced compressor error
Freezing (during cooling operation)/Overheating protection operation (during
P6
heating operation)
EE
Assembly error (system error)
P8
Pipe temperature error
E4
Communication error between wired remote controller and indoor unit
Pb
Indoor unit fan motor error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
U2
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1, Ud
Abnormal high pressure (63H worked)/Overheating protection operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal synchro-
U9, UH
nous signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Beep
Beep
Beep
n th
1 st
2 nd
· · · Repeated
Off
On
On
On
Approx. 2.5 s
0.5 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
Beep
Beep
Beep
2 nd
3 rd
n th
On
On
On
Off
0.5 s
0.5 s
0.5 s
Approx. 2.5 s
Symptom
Symptom
16
Beep
Beep
1 st
2 nd
· · · Repeated
On
On
On
Approx. 3 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
Remark
Remark
For details, check the LED
display of the outdoor
controller board.
Continued to the next page