Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
Number of blinks/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
received)
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Note: The supported check codes may vary depending on the connected outdoor unit.
Wireless remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
OCH616
Beep
Beep
Beep
1 st
2 nd
3 rd
On
On
On
0.5 s
0.5 s
0.5 s
Beep
1 st
On
On
Approx. 3 s
0.5 s
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Wired remote
controller
Check code
P1
Intake sensor error
P2, P9
Pipe (liquid or 2-phase pipe) sensor error
E6, E7
Indoor/indoor unit communication error
P4
Drain sensor error / Float switch connector open
P5
Drain overflow protection operation
PA
Forced compressor error
Freezing (during cooling operation)/Overheating protection operation (during
P6
heating operation)
EE
Assembly error (system error)
P8
Pipe temperature error
E4
Communication error between wired remote controller and indoor unit
—
—
Pb
Indoor unit fan motor error
Fb
Indoor unit control system error (memory error, etc.)
PL
Refrigerant circuit abnormal
Wired remote
controller
Check code
E9
Indoor/outdoor unit communication error
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
Compressor overcurrent interruption (When compressor locked)
U2
Abnormal high discharging temperature/49C worked/insufficient refrigerant
U1, Ud
Abnormal high pressure (63H worked)/Overheating protection operation
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan protection stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal synchro-
U9, UH
nous signal to main circuit/Current sensor error
—
—
—
—
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Beep
Beep
Beep
n th
1 st
2 nd
· · · Repeated
Off
On
On
On
Approx. 2.5 s
0.5 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
Beep
Beep
Beep
2 nd
3 rd
n th
On
On
On
Off
0.5 s
0.5 s
0.5 s
Approx. 2.5 s
Symptom
Symptom
16
Beep
Beep
1 st
2 nd
· · · Repeated
On
On
On
Approx. 3 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
Remark
Remark
For details, check the LED
display of the outdoor
controller board.
Continued to the next page