Field Setting - Daikin RXQ5M9W1B Installation Manual

Vrv ii system air conditioner
Hide thumbs Also See for RXQ5M9W1B:
Table of Contents

Advertisement

4
Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.
5
Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation
resistance of 2 MΩ or more is attained by applying a voltage of
500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.
6
Installation date
Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.

8.3. Field setting

If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.
Opening the switch box and handling the switches
When
carrying
out
field
remove the inspection cover (1).
Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.
Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.
Location of the dip switches, leds and buttons
1
Led H1~7P
2
Push button switches
BS1~BS5
3
Dip switch 1 (DS1: 1~4)
4
Dip switch 2 (DS2: 1~4)
5
Dip switch 3 (DS3: 1~2)
Led state
Throughout the manual the state of the leds is indicated as follows:
OFF
ON
blinking
Setting the dip switches
What to set with dip switch DS1
1
COOL/HEAT selector (refer to
transmission wiring and cool/heat selection" on page
(
OFF
= not installed = factory setting)
2~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS2
1~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS3
1+2
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
Installation manual
17
settings,
1
2
1
2
4
3
5
(only in case of a heat pump unit)
"Field line connection:
14)
Setting the push button switch (BS1~5)
Function of the push button switch which is located on the outdoor
unit PCB (A1P):
TEST:
C/H SELECT
MODE
HWL:
IND
H1P
H2P
H3P
BS1
BS2
MODE
SET
For changing the set mode
BS1 MODE
For field setting
BS2 SET
For field setting
BS3 RETURN
For test operation
BS4 TEST
For resetting the address when the wiring is changed or when
BS5 RESET
an additional indoor unit is installed
The figure shows state of the led indications when the unit is shipped
from the factory.
Setting the mode
The set mode can be changed with the
to the following procedure:
For setting mode 1: Press the
H1P led is off
.
For setting mode 2: Press the
5 seconds, the H1P led is on
If the H1P led is blinking
once, the setting mode will change to setting mode 1.
NOTE
If you get confused in the middle of the setting
process, push the
setting mode 1 (H1P led is off).
Setting mode 1
(not in case of cooling only unit)
The H1P led is off (COOL/HEAT selection setting).
Setting procedure
1
Push the
button and adjust the led indication to either
BS2 SET
one of the possible settings as shown below in the field marked
:
1
In case of COOL/HEAT setting by each individual outdoor unit
circuit.
2
In case of COOL/HEAT setting by the master unit when outdoor
units are connected in multiple system-combination
3
In case of COOL/HEAT setting by the slave unit when outdoor
units are connected in multiple system-combination
H1P
H1P
H2P
H2P
1
2
3
(*) It is necessary to use the optional external control adapter for
outdoor unit (DTA104A61/62). See the instruction delivered
with the adapter.
2
Push the
button and the setting is defined.
BS3 RETURN
L.N.O.P DEMAND
MASTER
SLAVE
H4P
H5P
H6P
H7P
BS3
BS4
BS5
RETURN
TEST
RESET
button according
BS1 MODE
button once, the
BS1 MODE
button for
BS1 MODE
.
and the
button is pushed
BS1 MODE
button. Then it returns to
BS1 MODE
(*)
.
(*)
.
H3P
H3P
H4P
H4P
H5P
H5P
H6P
H6P
RXQ5~10 + RXYQ5~48M9W1B
VRVII System air conditioner
4PW21816-1A
H7P
H7P

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents