10. Installation Instruction
10.1 Select the Best Location
10.1.1 Indoor Unit
•
There should not be any heat source or steam near
the unit.
•
There should not be any obstacles blocking the air
circulation.
•
A place where air circulation in the room is good.
•
A place where drainage can be easily done.
•
A place where noise prevention is taken into
consideration.
•
Do not install the unit near the door way.
•
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
•
Recommended installation height for indoor unit
shall be at least 2.5m.
10.1.2 Outdoor Unit
•
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation
from the condenser is not obstructed.
•
There should not be any animal or plant which
could be affected by hot air discharged.
•
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
•
Do not place any obstacles which may cause a
short circuit of the discharged air.
•
If piping length is over the rated length,
additional refrigerant should be added as shown
in the table below:
Model
Piping size
Rated
Length
Gas
Liqui
d
(m)
RE9JKX-1 9.52
6.35
7.5
(3/8")
(1/4")
RE12JKX-1 9.52
6.35
7.5
(3/8")
(1/4")
RE15JKX-1 12.7
6.35
7.5
(1/2")
(1/4")
Example: If the unit is installed at a 10m distance,
the quantity of additional refrigerant should be 50 g.
...... (10-7.5) m x 20g/m = 50 g
Max
Min
Max
Addition
Elevatio
Piping
Piping
al
n (m)
Length
Length
Refriger
(m)
(m)
ant
(g/m)
5
3
15
20
5
3
15
20
5
3
15
20
11.1.3 Indoor/Outdoor Unit
*This illustration is for explanation purposes only.
The indoor unit will actually face a different way.