1-12. Installing Distribution Joint

Pay special attention to any location, such as a basement, etc., where leaking refrigerant can
CAUTION
accumulate, since refrigerant gas is heavier than air.
(1) Refer to "HOW TO ATTACH DISTRIBUTION JOINT" enclosed with the optional distribution joint kit (CZ-P900PH1U,
CZ-P224BH1U, CZ-P680BH1U, CZ-P1350BH1U).
● When connecting a branch tubing to the indoor unit directly, it is necessary for each branch tubing to install at a positive angle
with respect to horizontal in order to prevent accumulation of refrigerant oil in stopped units. (See the below chart.)
Branch tubing system
How to install
branch tubing
B
* In case of common use solenoid valve kit
When connecting to A
A
B
A
D
Straight tubing
length over
Horizontal
8 in. (200mm)
Arrow view D
Vertical
Straight tubing
length over
8 in. (200mm)
15∼90°
Header branch system
Outdoor
Indoor
6.5 ft. (2m)
(From 1st branch to tip
of solidly welded part)
Horizontal line
Install at a positive angle
Restricted
Not restricted
When connecting branch tubing to indoor unit directly
Suction tube
When connecting to B
Straight tubing
length over
8 in. (200mm)
Horizontal
Straight tubing length
over 8 in. (200mm)
15∼90°
Vertical
Straight tubing
length over
Vertical
8 in. (200mm)
Vertical
(Main tubing is horizontal.)
Indoor
Horizontal line
Install at a positive angle
(15~30°)
Indoor
Solidly welded shut (X)
(15~30°)
Liquid tube / Discharge tube
15∼90°
15∼90°
or
15∼30°
15∼30°
(Branch tubing
angle)
Vertical
Vertical
15∼90°
● Be sure to solidly weld shut the T-joint end (marked by X in
the figure). In addition, pay attention to the insertion depth
of each connected tube so that the flow of refrigerant within
the T-joint is not impeded.
Be sure to use a commercial available T-joint.
● When using the header joint system, do not make further
branches in the tubing.
● Do not use the header joint system on the outdoor unit
side.
13
When not connecting
branch tubing to indoor
unit directly
Suction tube /
Discharge tube /
Liquid tube
Horizontal
0∼30°
(Branch tubing
angle)
Vertical
Vertical