Self-Diagnosis Method - Panasonic WH-SXC16F9E8 Service Manual

Hide thumbs Also See for WH-SXC16F9E8:
Table of Contents

Advertisement

16.5

Self-diagnosis Method

16.5.1 Connection Capability Rank Abnormality (H12)
Malfunction Decision Conditions:
During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to
determine connection capability rank abnormality.
Malfunction Caused:
1
Wrong model interconnected.
2
Wrong indoor unit or outdoor unit PCB (main) used.
3
Faulty indoor unit or outdoor unit PCB (main).
Abnormality Judgment:
Continue for 90 seconds.