Panasonic WH-SXC16F9E8 Service Manual page 36

Hide thumbs Also See for WH-SXC16F9E8:
Table of Contents

Advertisement

11.3.4.1
Wire Stripping and Connecting Requirement
Wire stripping
No loose strand
when insert
Tank Sensor Resistance Vs Temperature
16000
14000
12000
10000
8000
6000
4000
2000
Graph 5.1: Tank sensor characteristic
11.3.4.2
Connecting Requirement
For model WH-S**09*3E8
The equipment's power supply 1 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
For model WH-S**09/12/14/16*9E8
The equipment's power supply 1 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 complies with IEC/EN 61000-3-2.
The equipment's power supply 2 shall be connected to a suitable supply network, with the following maximum
permissible system impedance Z
ensure that power supply 2 is connected to a supply of the impedance or less.
Detail A
Indoor/outdoor
connecting
terminal board
5mm or
more
(gap between
wires)
0
-30
-20
-10
0
10
20
˚C
at the interface of the point: 0.449 Ω. Please liaise with supply authority to
max
Solar Pump Station Cable
(Optional)
Solar Three-way Valve
Cable (Optional)
External Control Cable
(Optional)
Tank Sensor Cable
(Optional)
Tank OLP Cable (Optional)
Room Thermostat Cable
(Optional)
Booster Heater Cord
(Optional)
Earth wire must be longer
than other cables for safety
reasons.
Three-way Valve Cable
(Optional)
Two-way Valve Cable
(Optional)
(*Cooling model only)
Conductor
fully insert
ACCEPT
Remove this
External Controller
jumper if External
Controller
(Optional) is
connected to the
indoor unit
30
Diagram 5.2: External Controller connecting
36
Conductor
Conductor not
over insert
fully insert
PROHIBITED
PROHIBITED
Switch (ON/OFF)
Terminal
17
18
diagram