16.5.32
Outdoor Current Transformer Open Circuit (F46)
Malfunction Decision Conditions:
A current transformer (CT) open circuit is detected by checking the compressor running frequency ( rated
frequency) and CT detected input current (< 0.65 A) for continuously 20 seconds.
Malfunction Caused:
1
CT defective.
2
Faulty outdoor unit PCB (main).
3
Compressor defective (low compression).
Abnormality Judgment:
Continue 3 times in 20 minutes.