Others - Toshiba RAS-M07G3DV Series Installation Manual

Hide thumbs Also See for RAS-M07G3DV Series:
Table of Contents

Advertisement

Optional wired remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
A
Terminal block for optional remote
B
controller wiring of indoor unit
NOTE
Even if the wireless remote controller of accessory parts connects with terminal block of indoor unit, it cannot be
used.
EN-31
Remote controller wire
Terminal block
(Locally procured)
A
Wired remote controller (Option)
B
9

Others

External static pressure settings
Change the external static pressure setting with the DIP
switch on the indoor unit P.C. board.
ON
OFF
SW501-2
SW501-1
MCU(IC501)
External static
SW501-2
pressure
10 Pa (default)
OFF
20 Pa
OFF
35 Pa
ON
45 Pa
ON
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF.
Remote Control A-B Selection
• When two indoor units are installed in the same room
or adjacent two rooms, if operating a unit, two units
may receive the remote control signal simultaneously
and operate. In this case, the operation can be
preserved by setting either one remote control to B
setting. (Both are set to A setting in factory shipment.)
• The remote control signal is not received when the
settings of indoor unit and remote control are different.
• There is no relation between A setting/B setting and A
room/B room when connecting the piping and cables.
– 16 –
To separate using of remote control for each indoor unit
in case of 2 air conditioners are installed near.
Remote Control B Setup.
1. Press TEMPORARY button on the signal receiving
unit to turn the air conditioner ON.
2. Point the remote control at the signal receiving unit.
3. Push and hold
button on the Remote Control by
the tip of the pencil. "00" will be shown on the display.
4. Press
during pushing
display and "00" will disappear and the air conditioner
will turn OFF. The Remote Control B is memorized.
Note : 1. Repeat above step to reset Remote Control to
be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from factory
is A.
SW501-1
OFF
ON
A
OFF
ON
Test Operation
To switch to the TEST RUN (COOL) mode, press
TEMPORARY button for 10 seconds. (The beeper will
make a short beep.) In the TEST RUN (COOL) mode, all
LEDs together keep blinking.
TEMPORARY button
In order to prevent a serial operation, the TEST RUN
(COOL) mode is released after 60 minutes have passed
and returns to the usual operation.
Installation Manual
. "B" will show on the
B
EN-32