Mitsubishi Electric PKA-A18HA6 Service Manual page 17

Split-system
Hide thumbs Also See for PKA-A18HA6:
Table of Contents

Advertisement

• Refer to the following tables for details on the check codes.
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blink
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
Number of blinks/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
B
e
e
p
OPERATION
INDICATOR
lamp blink
Off
pattern
Approx. 2.5 s
Self-check
starts
(Start signal
received)
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
14
[Output pattern B]
Errors detected by unit other than indoor unit (outdoor unit, etc.)
IR wireless remote controller Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Notes:
1 . If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on, there are no error records.
2 . If the beeper sounds 3 times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 seconds)" after the initial 2 beeps to confirm
the self-check start signal was received, the specified refrigerant address is incorrect.
OCH580
Beep Beep Beep
Beep
1
2
3
n
st
nd
rd
th
On
On
On
On
0.5 s
0.5 s
0.5 s
0.5 s
B
e
e
p
B
e
e
p
1
st
2
nd
On
On
On
Approx. 3 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Check code
P1
Intake sensor error
P2
Pipe (TH2) sensor error
P9
Pipe (TH5) sensor error
E6,E7
Indoor/outdoor unit communication error
P4
Float switch connector (CN4F) open
P5
Drain pump error
Forced compressor stop(due to water leakage abnormality)
PA
P6
Freezing/Overheating protection operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4, E5
Remote controller signal receiving error
Fb
Indoor unit control system error (memory error, etc.)
PL
Abnormality of refrigerant circuit
Remote controller transmission error
E0, E3
E1, E2
Remote controller control board error
Check code
Indoor/outdoor unit communication error
E9
(Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
UP
Open/short of outdoor unit thermistors
U3,U4
Compressor overcurrent interruption (When compressor locked)
UF
Abnormal high discharging temperature/49C operated/
U2
insufficient refrigerant
Abnormal high pressure (63H operated)/Overheating
U1,Ud
protection operation
Abnormal temperature of heatsink
U5
Outdoor unit fan protection stop
U8
Compressor overcurrent interruption/Abnormal of power module
U6
Abnormality of superheat due to low discharge temperature
U7
Abnormality such as overvoltage or voltage shortage and
U9,UH
abnormal synchronous signal to main circuit/Current sensor error
Others
Other errors (Refer to the technical manual for the outdoor unit.)
Beep Beep
1
2
· · · Repeated
st
nd
Off
On
On
Approx. 2.5 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
B
e
e
p
B
e
e
p
3
rd
n
th
On
On
Off
0.5 s
0.5 s
Approx. 2.5 s
S
y
m
p
o t
m
S
y
m
p
o t
m
17
Beep
Beep
1
st
2
nd
· · · Repeated
On
On
On
Approx. 3 s
0.5 s
0.5 s
Number of blinks/beeps in pattern indicates
the check code in the following table
R
R
For details, check
the LED display
of the outdoor
controller board.
As for outdoor
unit, refer to
outdoor unit's
service manual.