Mitsubishi Electric PKA-A18HA6 Service Manual page 30

Split-system
Hide thumbs Also See for PKA-A18HA6:
Table of Contents

Advertisement

System constraint
· This function is available only in cooling mode.
Ex.) Set temp. by R/C = 68°F [20:]
Set point = 79°F [26:]
When request code number is "323".
79°F
2nd unit Cut-in
[26:]
7.5°F
[4:]
71.5°F
2nd unit Cut-out
[22:]
68°F
[20:]
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)
NOTE
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
(1) Request Code List
Rotation setting
Setting No.
(Request code)
No.1
(310)
No.2
Rotation and Back-up OFF (Normal group control operation)
(311)
No.3
(312)
No.4
Rotation ON (Alternating interval = 1day) and back up function
(313)
No.5
Rotation ON (Alternating interval = 3day) and back up function
(314)
No.6
Rotation ON (Alternating interval = 5day) and back up function
(315)
No.7
Rotation ON (Alternating interval = 7day) and back up function
(316)
No.8
Rotation ON (Alternating interval = 14day) and back up function
(317)
No.9
Rotation ON (Alternating interval = 28day) and back up function
(318)
2
nd stage cut-in setting
Setting No.
(Request code)
No.1
Monitoring the request code of current setting
(320)
No.2
(321)
No.3
Cut-in Function ON(Set point = Set temp.+ 7.5°F [4°C])
(322)
No.4
Cut-in Function ON(Set point = Set temp.+ 10.8°F [6°C])
(323)
No.5
Cut-in Function ON(Set point = Set temp.+ 14.4°F [8°C])
(324)
OCH580
[2nd stage cut-in function]··· Request code number "322–324"
Main
unit
IC-1
Sub
unit
IC-2
Setting contents
Monitoring the request code of current setting
Back-up function only
Setting contents
Cut-in function OFF
Room temp. ] Set point
Start operation
Sub unit start operation
Run
Stop
Run
Initial
setting
Initial
setting
30
Room temp. < Set point −7.5°F [−4:]
Sub unit stop
Stop

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pka-a12ha6

Table of Contents