Mitsubishi Electric PKA-A18HA6 Service Manual page 16

Split-system
Hide thumbs Also See for PKA-A18HA6:
Table of Contents

Advertisement

9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
■IR wireless remote controller
CHECK
CHECK
display
TEMP
ON/OFF
ON/OFF
button
FAN
MODE
VANE
CHECK LOUVER
CHECK
TEST RUN
button
SET
RESET
CLOCK
OCH580
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the TEMP
Temperature
button
AUTO STOP
3. Point the remote controller at the
AUTO START
HOUR
sensor on the indoor unit and
button
press the HOUR button.
h
min
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
buttons.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation lamp
blinks, and the check code is
output.
(It takes 3 seconds at most for check
code to appear.)
• The check mode is cancelled.
16
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)