Inspection and check operation

Check operation

1) Use KEY MODE to run check operation .
- When the check operation is not completed, UP (unprepared) will appear on the LED after the communication check
and restrict compressor from operating . (UP Mode will be cleared automatically when check operation is completed . )
- Check operation may proceed from 30 minutes maximum 50 minutes depending on the operation status .
- During check operation, noise can be generated due to vavle inspection . (Check the product if abnormal noise occurs
continously)
2) When error occurs during check operation, check the error code and take appropriate measures .
- Refer to service manual if you need inspection or when other errors occur .
3) When check operation ends, use S-NET pro or S-CHECKER to issue a result report .
- Refer to service manual for further actions if you have any items with "inspection required" sign on the result report .
- After taking appropriate measure for the items with "inpection needed" sign, run the check operation again .
4) Check the following itmes by running (cooling/heating) trial operation .
- Check if cooling/heating operation performs normally .
- Individual indoor unit control: Check for air flow direction and fan speed .
- Check for abnormal operation noise from the indoor and outdoor unit .
- Check for proper draining from the indoor unit during cooling operation .
- Use S-NET pro to check the detail operation status .
5) Explain to the user how to use the air conditioner according to the user's manual .
6) Hand over the installation manual to the customer so they can keep it with them .
Automatic refrigerant amount detection function (Checking th amount of refrigerant)