Refrigerant pipe installation
Connection by header joint
Outdoor unit
Header joint
Connection by Y-joint/header joint
Outdoor unit
Y-joint
H1
Indoor unit
Classification
Maximum
Outdoor
allowable
unit ~
length of
Indoor units
pipe
Maximum
Outdoor
allowable
unit ~
height
Indoor units
Maximum allowable
length after Y-joint
❋ ❋ When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90m (295'), upgrade the low
pressure pipe of the main pipe one step .
20
AM0@@FXMDCH_IM_EN_03408A(1).indd 20
g
Indoor unit
Header joint
g
f
H2
c
Header joint connection
The distance between an outdoor unit and the farthest indoor unit ≤ 150m (492')
Actual
Ex) 8 indoor units
Length
a+g≤ 150m (492')
Equivalent
The distance between an outdoor unit and the farthest indoor unit ≤ 175m (574')
length
Main pipe
The main pipe(a) from the outdoor unit to the first Y-joint should be less than 110m
length
(361') .
Total
The sum of total length of pipes should be less then 300m (984') .
length
Height
H1: The difference in height between an outdoor unit and indoor unit < 50m (164')
Height
H2: The difference in height between indoor units ≤ 15m (49')
The distance between the header joint
Actual
and the indoor unit ≤ 40m (131')
Length
Ex) b, c ~ f, g ≤ 40m (131')
Y-joint / header joint connection
Ex) 8 indoor units
a+b+c ≤ 150m (492')
The distance between the first Y-joint and
the farthest indoor unit ≤ 40m (131')
Ex) 8 indoor units
b+c, d+g ≤ 40m (131')