Refrigerant pipe work
Refrigerant Y-joint installation
Install the Y-joint 'horizontally' or 'vertically' .
X Install horizontally
X
X Install vertically
X
• When using A~J type of Y-joint, connect the Y-joint to the pipe with the provided reducer .
• When using K~Z type of Y-joint, connect the Y-joint to the pipe by cutting the inlet of the Y-joint or provided
NOTE
reducer properly .
• Install the Y-joint within ±15° on the horizontal or on the vertical .
• Make sure that the pipe does not break at Y-joint and pipe connection .
CAUTION
• Keep a minimum straight line distance of 500mm (20 inch) or more before connecting Y- joint .
Reducer
Pipe
Connect to
outdoor unit
AM0@@FXMDCH_IM_EN_03408A(1).indd 21
Connect to other branch
Rear
joint or indoor unit
Pipe connection
Reducer
Rear
Gas/liquid side Y-joint
Front
❋ ❋ Install the Y-joint within ±15° on the
horizontal or on the vertical .
10~15mm (0 . 3 9~0 . 5 9 inch)
or more
Main pipe
Minimum straight line distance
[500mm (20 inch) or more]
21