8-5. Cold Draft Prevention (Heating)
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat
exchange coil have sufficiently warmed up.
Indoor fan speed varies according to the indoor heat exchange coil temperature as table shown below.
Condition
Compressor is in operation
(Indoor coil temp. goes up)
Compressor is stopped
(Indoor coil temp. goes down)
NOTE
1 When the coil temperature rises above 36°C, indoor fan operates in set speed. At the same time,
standby lamp on front of the indoor unit lights OFF.
2 If 10 minutes has elapsed after the compressor has been stopped, the indoor fan stops its operation
regardless of the indoor heat exchange coil temperature.
36°c
Indoor heat
30°c
exch. coil
temp.
25°c
20°c
Set Speed
Low
Indoor fan
OFF
Standby lamp
Compressor
Indoor coil temperature (°C)
between 25 to 30°C
between 30 to 36°C
Compressor : ON
when the coil
temp. goes up
LL
UL
ON
OFF
below 25°C
over 36°C
over 20°C
below 20°C
OFF
ON
38
Indoor fan speed
OFF
LL (Very low)
Low
Set speed
1
UL (Ultra low)
OFF
2
Compressor : OFF
when the coil
temp. goes down
ON
OFF
Set Speed
Low
LL
UL
OFF