9-4. Air conditioner operates, but abnormalities are observed.

9-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT).
• Remote control unit may be defective.
• Measure resistance of 4–way valve's
winding.
COOL
HEAT
• Check voltage between terminals
No.2 and No.5 at the terminal plate.
(AC 220 - 240V)
• Indoor PCB Ass'y is defective.
HEAT
COOL
• Check voltage between terminals
No.2 and No.5 at the terminal plate.
No voltage appears.
(0V)
Receiver in lamp Ass'y may be
defective.
• Check to see if switching sound (click)
is heard from 4–way valve's body.
50