Programming
Continuous pump operation
(809, 1109, 1409)
Overtemp prot pump circuit
(820, 1120, 1420)
Mixing valve boost
(830,1130, 1430)
Actuator running time
(834, 941, 1134)
Floor curing function
(850, 1150, 1450)
86
Using the continuous pump operation function switching off the pump can be
suppressed by the quick setback and when reaching the room set point (room
thermostat, room sensor or room model)
- No: the heating circuit pump /boiler pump can be switched off by quick setback
or reaching the room set point
- Yes: the heating circuit pump/boiler pump remains switched on even during
the quick setback and after reaching the room set point
This function prevents overheating of the pumped heating circuit by switching-
on and switching-off the pump, if the flow temperature is higher than the flow
temperature required according to the heating curve (e.g. in case of higher de-
mands of other consumers).
The heat demand of the mixer heating circuit to the generator is superelevated
above the set value here. This boost should be achieved so that the temperature
fluctuations can be corrected with the mixer valve.
For mixing circuits, a kick-start of the mixer drive is carried out after a pump kick-
start (Pump is OFF). In this case, the mixer will be controlled in direction OPEN
and CLOSED.
The time of activation in direction OPEN corresponds to the drive running time.
The floor curing function serves controlled drying out of screed floors
- Off: the function is switched off.
- Functinal heating (Fh): Part 1 of the temperature profile will be run through au-
tomatically.
- Curing heating (Ch): Part 2 of the temperature profile will be run through auto-
matically.
- Functional- and curing heating: The whole temperature profile will be run
through automatically.
- Manually: control to the Floor curing setpoint manually.
Fig. 19: Temperature profile during floor curing function
x
Fh
X
Start day
Fh Functional heating
Ch Curing heating
Paramount three 30-115 kW
Ch
Fh+Ch
[day]
7308272-03 03.14