Potterton Paramount three 30 Installation Manual page 56

Hide thumbs Also See for Paramount three 30:
Table of Contents

Advertisement

Programming
Function
Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Flow temp setpoint room stat
Delayed heat request
Room influence
Room temp limitation
Boost heating
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
Optimum start control max
Optimum stop control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit
Off | On
Mixing valve boost
Actuator running time
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
Floor curing setp manually
Floor curing setp current
Floor curing day current
Excess heat draw
Off | Heating mode | Always
With prim contr/system pump
No | Yes
Pump speed reduction
Operating level | Characteristic
Pump speed min
Pump speed max
Curve readj at 50% speed
Flow setp readj speed ctrl
No | Yes
Operating level changeover
Frost protection | Reduced | Comfort
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
Heating circuit 3
Parameter only visible, if heating circuit 3 exists!
Comfort setpoint
Reduced setpoint
56
Prog.
1030
1032
1040
1041
1042
1046
1050
1060
1070
1080
1090
1091
1100
1101
1120
1130
1134
1150
1151
1155
1156
1161
1172
1180
1182
1183
1188
1190
1198
1200
1310
1312
Paramount three 30-115 kW
Standard value
1)
Level
no.
Eu
18°C
E
0 °C
E
8°C
E
80°C
E
--- °C
E
0 s
C
- - - %
E
0.5°C
E
--- °C
E
Down to reduced set-
point
E
0 min
E
0 min
E
--- °C
E
-15°C
E
Off
E
5°C
E
120 s
E
Off
E
25°C
E
--- °C
E
0
E
Heating mode
E
yes
E
Characteristic
C
30 %
C
80 %
E
10 %
E
No
E
Reduced
E
Protection
Eu
20.0°C
Eu
18.0°C
7308272-03 03.14