Test Operation - Carrier 42TSV052P1 Installation Manual

Hide thumbs Also See for 42TSV052P1:
Table of Contents

Advertisement

10.2
The Specification of Power
(Refer to Table10-1)
Wiring figure
10.3
(Refer to Fig.10-4)
10.4 Outdoor unit
Remove the electric parts cover from the outdoor unit.
1.
2.
Connect the connective cables to the terminals as identified
with their respective matched numbers on the terminal block
of indoor and outdoor units. (Connective cable sheath
length to be removed and insert into the terminal block.)
3.
To prevent the ingress off water, from a loop of the
connective cable as illustrated in the installation diagram of
indoor and outdoor units.
4.
Insulate unused cords (conductors) with PVC-tape. Process
them so they do not touch any electrical or metal parts.
10mm
5.
The U type plug or circular type plug must be added to wiring
terminal. (refer to Fig.10-3)
CAUTION
Wrong wiring connections may cause some electrical parts to
malfunction.
The Specification of Power for the invert type air conditioner(independence power supply)
Table 10-1
MODEL
PHASE
POWER
(indoor)
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
PHASE
POWER
(outdoor)
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
Cord wire
40mm
Fig.10-2
Fig.10-3
42TSV052P1
38TSV052P1
1 P h a s e
220-240 V
15/10
1 P h a s e
220-240 V
30/20

11. TEST OPERATION

1
The test operation must be carried out after the entire
installation has been completed.
Please confirm the following points before the test operation:
2
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of
the refrigerant have been recorded.
The power voltage fits the rated voltage of the air
conditioner.
There is no obstacle at the outlet and inlet of the outdoor
and indoor units.
The gas-side and liquid-side stop valves are both opened.
The air conditioner is pre-heated by turning on the power.
According to the user's requirement, install the remote
3
controller frame where the remote controller's signal can
reach the indoor unit smoothly.
Test operation
4
Set the air conditioner under the mode of "COOLING" with the
remote controller, and check the following points. If there is
any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
1) The indoor unit
a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works
well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
operation
I. Whether the air conditioner heats well in the case of the
HEATING/COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during
operation.
b. Whether the generated wind, noise, or condensed of by
the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked.
42TSV067P1
42TSV080P1
38TSV067P1
38TSV080P1
1 P h a s e
1 P h a s e
220-2 40V
220-2 40V
15/10
15/10
1 P h a s e
1 P h a s e
220-240 V
220-240 V
30/20
40/30
42TSV110P1
42TSV130P1
38TSV110P1
38TSV130P1
1 P h a s e
1 P h a s e
220-2 40V
220-2 40V
15/10
15/10
1 P h a s e
1 P h a s e
220-240 V
220-240 V
40/35
40/35
installation manual
15