Refrigerant Pipe - Carrier 42TSV052P1 Installation Manual

Hide thumbs Also See for 42TSV052P1:
Table of Contents

Advertisement

Table 6-1
MODEL
A
B
C
38TSV
845
560
335
052P1
38TSV
900
590
333
067P1
38TSV
990
624
366
080P1
38TSV
938
634
404
110P1
38TSV
938
634
404
130P1
6.3 Space of installation and maintenance
Split type
outdoor unit
(Wall or obstacle)
Air inlet
>30cm
N
Air inlet
M
All the figures in this manual are for explanation
purpose only. They may be slightly different from the air
conditioner you purchased.
6.4 Moving and installation
Since the gravity center of the unit is not at its physical
center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from
deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of
the outdoor units.(Refer to Fig.6-6)
Fasten the feet of this unit with bolts firmly to prevent it from
collapsing in case of earthquake or strong wind.(Refer to
Fig.6-6)
18
24
36
36
Fix with bolt
48
60
installation manual
10
mm
D
E
F
H
360
312
320
700
Fig.6-2
355
302
315
860
Fig.6-2
396
340
354
966
Fig.6-2
448
368
392
1369
Fig.6-3
448
368
392
1369
Fig.6-3
Maintain channel
>60cm
P
Air outlet
Fig.6-5
NOTE
The actual unit shall prevail.
Fig.6-6
NOTE
All the pictures in this manual are for explanation
purpose only. They may be slightly different from the
air conditioner you purchased(depend on model).The
actual shape shall prevail.
Concrete Foundation
1
Foundation could be on flat and is recommended be 100-300mm
higher than ground level.
2
Install a drainage around foundation for smooth drain
3
When installing the outdoor unit fix the unit by anchor bolts of
M10.
4
When installing the unit on a roof or a veranda,drain water
sometimes turns to ice on a cold morning. Therefore, avoid
draining in an area that people often use because it is slippery.
Table 6-4
No
Description
1
Outdoor Unit
2
Vibration-proof rubber
3
Anchor Bolt M10
4
Drainage (Wide 100×Depth 150)
5
Drainage
6
Mortar Hole (Φ100×Depth 150)

7. REFRIGERANT PIPE

7.1 Vacuum with vacuum pump
1)
Use the vacuum pump which vacuum level lower than
-0.1MPa and the air discharge capacity above 40L/min.
2)
The outdoor unit is not necessary to vacuum, don't open the
outdoor unit gas and liquid pipe shut-off valves.
3)
Make sure the vacuum pump could result as -0.1MPa or
below after 2 hrs or above operation. If the pump operated 3
hrs or above could not achieve to -0.1MPa or below, please
check whether water mix or gas leak inside of the pipe.
≥100
Fig.6-7