Condenser Fan Motor Not Operating; Agitator Motor Not Operating - Cornelius AURORA 10,000 PLUS Installation Manual

Cooling unit
Table of Contents

Advertisement

Trouble
CONDENSER FAN MOTOR
NOT OPERATING
AGITATOR MOTOR NOT
OPERATING
1593
Probable Cause
A.
Jumper cord loose or
disconnected from condenser
fan motor or terminals inside
control box. Broken wire in
cord.
B.
Fan blade obstructed
C.
Inoperative condenser fan
motor
D.
Blown power circuit fuse.
E.
Condenser Cooling Unit
contactor inoperable.
A.
Agitator motor propeller
obstructed.
B.
Low voltage
C.
Loose, disconnected, or
broken wiring.
D.
Inoperative agitator motor.
46
Remedy
A.
Tighten connections or replace
cord
B.
Remove obstruction.
C.
Replace condenser fan motor.
D.
Replace power circuit fuse.
E.
Replace Cooling Unit contactor.
A.
Remove obstruction.
B.
Voltage must be at least 208 V
(60 HZ) or 230V (50 HZ) at
compressor terminals when
compressor is trying to start.
C.
Tighten connections or replace
broken wiring.
D.
Replace agitator motor.