8.2.

Capacity And Power Consumption

8.2.1.

Cooling performance

CS-F24DTE5 / CU-L24DBE5
CS-F28DTE5 / CU-L28DBE5
CS-F34DTE5 / CU-L34DBE5
CS-F43DTE5 / CU-L43DBE5
CS-F50DTE5 / CU-L50DBE5
Calculation of actual cooling capacity and power consumption:
Example: CS-F24DTE5 / CU-L24DBE5
Calculation of the actual cooling capacity and power consumption for the following cooling conditions;
Indoor temperature of 27/19°C and outdoor temperature of 40°C (Standard condition).
Calculation method
1.
Find the cooling capacity ratio and the power consumption ratio from the cooling capacity graph and power consumption graph for model CS-
F24DTE5 / CU-L24DBE5.
The cooling capacity ratio indicate at the intersection between an outdoor unit air inlet temperature of 40°C on the horizontal axis and an
indoor unit air inlet temperature on 27/19°C is 0.95.
The cooling power consumption ratio from the same intersection on the power consumption graph is 1.03.
2.
Thus,
Actual cooling capacity = cooling capacity ratio x rated cooling capacity = 0.95 x 6.5 = 6.18 (kw).
Actual cooling power consumption = cooling power consumption x rated power consumption = 1.03 x 2.45 = 2.52 (kw).
Model name
Max cooling capacity
Max capacity (kw)
Max power consumption (kw)
6.5
7.5
12
13.5
16
21
2.3
2.45
3.4
4.3
5.1