Contact Details Please note that some of the contact details on this PDF document may not be current. Please use the following details if you need to contact us: Telephone: 0844 879 3588 Email: customer.services@gdcgroup.co.uk The Help Centre section of this website also features a wide range of information which may be of use to you and is available 24 hours a day. It includes: • Manuals and guides downloads • Servicing • Where to buy our products • Literature downloads www.robinsonwilley.co.uk/help A division of GDC Group Ltd Registered No: 1313016 England VAT GB 287 1315 50004 Millbrook House Grange Drive Hedge End Southampton SO30 2DF EEE Producer Registration Number –...
991039 Issue 8 with SAFEGUARD Installation & Servicing Instructions LEAVE THESE INSTRUCTIONS AT OR NEAR THE USER'S METER FOR USE ON FUTURE SERVICE CALLS SERVICE AND INSTALLATION...
Notified Body No.0086. The efficiency value may be used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The above exceeds the minimum requirement of 63%. Firegem Visa Super Deluxe Hieght: 556mm (22in)*...
Page 4
NOTE: Where a spigot extension is fitted it may be extended upto 152mm (6in) from the back of the fire. A spigot extended to this specification is available from Robinson Willey, Part No. 991134. It must be cut down to suit the application.
FIT THE CLOSURE PLATE Fit the closure plate and seal to the fire surround along the edges, but ensure that the relief opening is NOT covered. If the fireplace opening is too large for the closure plate to fit snugly, the closure plate must be extended to suit. The minimum fireplace opening when wall mounting will have an actual height of 413mm (16.25in), and the top of this opening must be at least 510mm (20.1in) above the floor.
PRE-CAST FLUES (a) The fire is suitable for fitting into properly constructed non-impeded pre-cast flues of cross section 198mm x 67mm or equivalent cross sectional area with no dimension less than 63mm, which comply with the recommendations of BS 5440:Pt 1 and BS 1289, and have a minimum equivalent height of 3m (10ft).
Min. Distance 150mm (6in) CONNECT TO GAS SUPPLY 1.MAKE GAS CONNECTION The gas inlet pipe and inlet union are readily accessible under the base of the fire. Provision is made for right hand, left hand or concealed connections by rotation of the elbow prior to tightening the flared tube and nut connection. The elbow has a Rp1/4 (1/4in B.S.P .) thread for the supply pipe.
Page 8
6. TEST FOR SPILLAGE (See Fig. 6) Light the fire and leave on at full rate. Close all doors and windows in the room and after the fire has been alight for five minutes insert a lighted smoke match tube under the firebox canopy at either end.
NOTES ON SERVICING Access to all connections, radiants, injectors etc. is given by removing the front panel. The panel is removed by lifting upwards to clear the lower supports and then pulling forward and downward away from the fire. NOTE: For thermocouple or electrode replacement it is necessary to exchange the pilot assembly. N.B.: For problems with small or no pilot flame always try a new filter first.
Page 10
6.REPLACING SPARK GENERATOR Disconnect all three leads and remove the battery. Remove the fixing screws (2 off) one at the front and one at the right hand side. Lift out the spark generator complete with mounting bracket. Transfer mounting bracket to the new spark generator. Replace in reverse order.
Control Knob Adaptor (see page 7) Robinson Willey GDC Group Ltd, Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF. Telephone: 0844 879 35 88 E-mail: info@robinsonwilley.co.uk website: www.robinsonwilley.co.uk Robinson Willey is a Trading Division of the GDC Group Ltd...