Protec 6000PLUS/OP/S Installation And Service Instructions

Advertisement

Quick Links

Overview
The Protec 6000PLUS/OP/S is a loop powered fire sensor, which reports smoke in its installed location to the fire alarm control
panel. The sensor is also equipped with an integrated loop powered programmable electronic sounder and an integrated loop
isolator.
Technical Specification
Loop protocol
Loop isolator fitted
Loop voltage range
Loop average quiescent current (24V loop)
Loop average alarm current ( 24V loop )
Analogue values
Indications
Environmental operational limits
Sounder Frequencies
Sounder synchronisation
IP rating
Isolator Specification
Installation
1. Base options: 6000PLUS/BASE
6000PLUS/FFBASE
28-075-01 (Plug and Play Fast Fix)
28-075-02 (Plug and Play Surface)
Note: See individual information sheets for base wiring details.
2. Install the detector in the base, turn firmly clockwise.
Commissioning
1. Each 6000PLUS detector has a unique serial number which will be used as part of the commissioning of the fire alarm
system. It is necessary to remove one of the 'peelable ' bar code labels present on the product and place it in the
commissioning booklet supplied with each Protec addressable control panel. The bar code sticker should be placed at the
relevant loop and address position intended. It is important that serial numbers are not mixed otherwise the addressing of
the 6000PLUS/OP/S will be incorrect when commissioned.
2. Commission the device onto the system as detailed in the installation and commissioning manual for the fire alarm panel
being used.
6000PLUS/OP/S Certification Details
EN 54 - 3: 2001 + A1 + A2
Alarm devices - Sounder
Type A: For indoor use
6000PLUS/OP/S
High sensitivity
Not approved.
DEL2093 Issue 4 02/11 SB
6000PLUS/OP/S Installation, Commissioning and Service Instructions
Protec Algo-tec™ 6000PLUS
Yes
18 to 27V Algo-tec™ loop
0.4mA
5mA
Smoke
Normal 40 to 60 bits
Fault Low <35 bits
Fault low High>90 bits
On-board red indicating LED
-10 to 50 degrees C ( 95% RH no condensation or icing )
Continuous 990Hz, Warble 730Hz to 990Hz, Pip 990Hz
Sounder synchronisation is achieved by panel control
IP21C
Please see Protec DEL2110 for details
EN Standards Compliance/ Approvals table
0 8 3 2
Protec Fire Detection plc, Nelson, Lancashire, England, BB9 6RT
0832-CPD-1185
EN 54 - 7
Point type smoke detector
6000PLUS/OP/S
Technical Data included in this datasheet DEL2093 Issue 4
Medium Sensitivity
EN 54 - 7: 2000 + A1: 2002 + A2: 2006
Page 1 of 3
LPCB Approved as part of product approval
LPCB Approved as part of product approval
LPCB Approved as part of product approval
LPCB Approved as part of product approval
10
Low Sensitivity
Not approved.
Copyright © Protec Fire Detection plc 201 0
EN 54 - 17: 2005
Short-circuit isolator
6000PLUS/OP/S

Advertisement

loading
Need help?

Need help?

Do you have a question about the 6000PLUS/OP/S and is the answer not in the manual?

Questions and answers

Summary of Contents for Protec 6000PLUS/OP/S

  • Page 1 Overview The Protec 6000PLUS/OP/S is a loop powered fire sensor, which reports smoke in its installed location to the fire alarm control panel. The sensor is also equipped with an integrated loop powered programmable electronic sounder and an integrated loop isolator.
  • Page 2 Test the operation of the integral sounder. • Remove old service label and fit new label to detector. • DEL2093 Issue 4 02/11 SB Page 2 of 3 Copyright © Protec Fire Detection plc 201 0...
  • Page 3 6000PLUS/OP/S Installation, Commissioning and Service Instructions Polar outputs and profiles (sounder) DEL2093 Issue 4 02/11 SB Page 3 of 3 Copyright © Protec Fire Detection plc 2010...