Lennox MPA012S4S-1L Service Manual page 255

Mini-split systems
Table of Contents

Advertisement

Capacity Area
Norm Code (N)
Model
9K
HP
1.0
Outdoor Temperature (T4)
<0°C
<12°C
Heating
<32°F
<53.6°F
Modify
120%
80%
Rate
When there more than one indoor unit:
Outdoor Temperature (T4)
<0°C
<12°C
Heating
<32°F
<53.6°F
Modify
120%
100%
Rate
NOTE - The fi nal result is integer.
Then modify it according to T2 average (correction):
NOTE - Average value of T2: Sum T2 value of all
indoor units)/ (indoor units number).
According to the fi nal capacity request to confi rm the
operating frequency, as following table.
Heating capacity improved in low ambient heating
a
b
c
d
e
3
2
1.5
1
.5
12K
18K
1.2
1.5
12°C to 17°C
≥17°C
53.6°F to 77°F
≥62.6°F
40%
20%
12°C to 17°C
53.6°F to 62.6°F ≥62.6°F
80%
In heating mode, when T2<T2_ExitT4LowFre_
f
ADD , and T4<-4°C, there is frequency elevation:
0
elevated frequency= Recent frequency * 110%
Frequency
(Hz)
Amendatory
capacity
demand
When T2> T2_ExitT4LowFre_ADD-2 and T4>-6,
the highest frequency can't exceed F17
When T2> T2_ExitT4LowFre_ADD-4 and T4>-8,
the highest frequency can't exceed F18
When T2> T2_ExitT4LowFre_ADD-6 and T4>-10,
the highest frequency can't exceed F19
≥17°C
In the other conditions, the highest frequency is
60%
F20
...
HEAT_
HEAT_
0
F1
F2
...
...
0
1
2
...
Lennox Mini-Split Service Manual / Page 255