Viessmann VITOGAS 100-F Service Instructions Manual page 9

Rated heating output of 29 to 60 kw gas boiler natural gas and lpg version
Table of Contents

Advertisement

Further details regarding the individual steps
10. Remove the pressure gauge and
seal test nipple A with screw.
Supply pressure (flow pressure):
Natural gas
Below 8 mbar
8 to 25 mbar
Above 25 mbar
LPG
Below 27.7 mbar
27.7 to 57.5 mbar
Above 57.5 mbar
Commissioning, inspection, maintenance
11. Open the gas shut-off valve and
check test nipple A for gas tight-
ness.
Danger
Gas escaping from the test
nipple leads to a risk of
explosion.
Check the test nipple for gas
tightness.
Action
■ Do not commission the boiler
■ Notify your gas supply utility or your
LPG supplier
Commission the boiler
■ Install a separate gas pressure gover-
nor upstream of the system
■ Setting the pre-charge pressure:
20 mbar for natural gas
30 mbar for LPG
■ Notify your gas supply utility or your
LPG supplier
(cont.)
9